Effects analysis of the pollution layer parameters on a high-voltage porcelain cylindrical insulator using response surface methodology

被引:0
作者
BELHOUCHET K. [1 ]
BAYADI A. [2 ]
ALTI N. [2 ]
OUCHEN L. [2 ]
机构
[1] Department of Electrical Engineering, Faculty of Technology, Mohamed Boudiaf University, M'sila
[2] Department of Electrical Engineering, Faculty of Technology, Ferhat Abbas University, Setif - 1
来源
Diagnostyka | 2021年 / 22卷 / 02期
关键词
Electric field; Finite element method; Insulators; Pollution; Response surface methodology;
D O I
10.29354/DIAG/134114
中图分类号
学科分类号
摘要
The influences of the pollution layer parameters including; conductivity Position and length on the performance of high-voltage cylindrical insulator were investigated. Parameters effects and their interactions have been assessed and determined using the variance statistical technique and the relation between parameters and the flashover voltage maximum electric field and the breakdown strength is modeled by the response surface methodology (RMS). The 3D model from Comsol Multiphysics was used for modeling and the FEM method was utilized for simulations. The findings demonstrate that the flashover voltage of the non-uniformly contaminated surface is primarily affected by the pollution layer length. Simulation results show that the intensity of the electric field rises with the increasing in length of pollution layer and its position. It was noted that the experimental tests in laboratory for non-uniform contamination are in strong alignment with simulation studies. The results of this analysis should expand our understanding about the performance of outdoor insulators under specific contaminated conditions. The knowledge gathered can be used to enhance the configuration of insulators used in contaminated regions and it is believed that the current study has resulted methodology to estimate reliably and realistically the pollution performance of cylindrical porcelain insulators. © 2021 Polish Society of Technical Diagnostics. All rights reserved.
引用
收藏
页码:21 / 28
页数:7
相关论文
共 14 条
[1]  
Belhouchet K, Bayadi A, Bendib ME., Artificial neural networks and genetic algorithm modelling and identification of arc parameter in insulators flashover voltage and leakage current, International Journal of Computer Aided Engineering and Technology, 11, 1, pp. 1-13, (2019)
[2]  
Polluted insulators: A Review of Current Knowledge, (2000)
[3]  
Gorur R, Olsen R., Prediction of flashover voltage of insulators using low voltage surface resistance measurement, Power System Engineering ResearchCenter, (2006)
[4]  
Sahli Z, Mekhaldi A, Boudissa R, Boudrahem S., Prediction parameters of dimensioning of insulators under non-uniform contaminated conditions by multiple regression analysis, Electrical Power System Research, 81, 4, pp. 821-829, (2011)
[5]  
Rizk FAM., Mathematical Models for Pollution Flashover, Electra, 78, pp. 71-103, (1981)
[6]  
Boeme H, Obenhaus F., Pollution flashover tests on insulators in the laboratory and in systems and the model concept of creepage -path flashover, CIGRE, 11, (1966)
[7]  
Alston LL, Zoledziowski S., Growth of discharges on polluted insulation, Proc. IEE, 110, 7, pp. 1260-1266, (1963)
[8]  
Wilkins R., Flashover voltage of HV insulators with uniform surface pollution film, Proc. IEE, 116, 3, pp. 457-465, (1969)
[9]  
Belhouchet K, Bayadi A, Belhouchet H, Romero M., Improvement of mechanical and dielectric properties of porcelain insulators using economic raw materials, Boletín de la Sociedad Española de Cerámica y Vidrio, 58, 1, pp. 28-37, (2019)
[10]  
Slama ME, Beroual A, Hadi H., Influence of the linear non-uniformity of pollution layer on the insulator flashover under impulse voltage - estimation of the effective pollution thickness, IEEE Trans. Dielectr. Electr. Insul, 18, 2, pp. 384-392, (2011)