Development of mechanical CBM system for electromagnetically actuated vacuum circuit breaker

被引:0
|
作者
Yano T. [1 ]
Matsunaga T. [2 ]
Arioka M. [2 ]
Koyama K. [3 ]
Takeuchi T. [4 ]
机构
[1] Advanced Technology R and D Center, Mitsubishi Electric Corporation, 8-1-1, Tsukaguchi-Honmachi, Amagasaki
[2] Power Distribution Systems Center, Mitsubishi Electric Corporation, 8, Horai-cho, Marugame
[3] Information Technology R and D Center, Mitsubishi Electric Corporation, 5-1-1, Ofuna, Kamakura
[4] Fukuyama Works, Mitsubishi Electric Corporation, 1-8, Midorimachi, Fukuyama
来源
Yano, Tomotaka (Yano.Tomotaka@ap.MitsubishiElectric.co.jp) | 1600年 / Institute of Electrical Engineers of Japan卷 / 136期
关键词
Condition based maintenance; Electromagnetic actuator; Vacuum circuit breaker;
D O I
10.1541/ieejpes.136.192
中图分类号
学科分类号
摘要
A new mechanical CBM (Condition Based Maintenance) system for an electromagnetically actuated vacuum circuit breaker (VCB) has been developed. This CBM function has a new monitoring method using analysis of the coil current profile of the actuator operation. The VCB has three sets of vacuum interrupters, insulating rods, contact pressure springs and electromagnetic actuators. The electromagnetic actuators control each phase independently. We have clarified the variation in the actuator's current profile by the developed analytical method when the value of friction, contact erosion and driving capacitance changes. We have established a diagnostic method for the mechanical condition using this current profile analysis. With this method, a new remote monitoring system of the mechanical condition using current monitors on the actuator's controller has been developed and mounted on VCB for cubicle type gas insulated switchgears rating from 7.2 kV to 84 kV The maintenance for mechanical parts of VCB changes to the CBM system from the conventional TBM (Time Based Maintenance) system using this monitoring system. The developed mechanical CBM system significantly reduces the life cycle cost including the labor cost of maintenance. © 2016 The Institute of Electrical Engineers of Japan.
引用
收藏
页码:192 / 197
页数:5
相关论文
共 50 条
  • [1] Development of Mechanical CBM System for Electromagnetically Actuated Vacuum Circuit Breaker
    Yano, Tomotaka
    Matsunaga, Toshihiro
    Arioka, Masahiro
    Koyama, Kenichi
    Takeuchi, Toshie
    ELECTRONICS AND COMMUNICATIONS IN JAPAN, 2017, 100 (02) : 50 - 57
  • [2] Development of electromagnetically actuated vacuum circuit breaker for 72 kV rated switchgear
    Kim, Tae-Hyun
    Tsukima, Mitsuru
    Maruyama, Akihiko
    Takahara, Osamu
    Haruna, Kazushi
    Yano, Tomotaka
    Matsunaga, Toshihiro
    Imamura, Kazuaki
    Arioka, Masahiro
    Takeuchi, Toshie
    IEEJ Transactions on Power and Energy, 2008, 128 (12) : 1459 - 1464
  • [3] On-line Monitoring System for Mechanical Characteristics of Vacuum Circuit Breaker
    Liu, Guixin
    Tian, Yu
    Pan, Zhaoyang
    Dong, Enyuan
    Zou, Jiyan
    PROCEEDINGS OF THE 2015 INTERNATIONAL CONFERENCE ON INTELLIGENT SYSTEMS RESEARCH AND MECHATRONICS ENGINEERING, 2015, 121 : 1100 - 1104
  • [4] Development of a novel DC vacuum circuit breaker
    Dong, EY
    Zou, JY
    Cong, JY
    ISDEIV: XXITH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM, VOLS 1 AND 2, PROCEEDINGS, 2004, 21 : 629 - 631
  • [5] Development of the vacuum circuit breaker with an electromagnetic actuator
    Morita, Ayumu
    Yabu, Masato
    Kajiwara, Satoru
    IEEJ Transactions on Power and Energy, 2007, 127 (02) : 397 - 402
  • [6] Development of HVDC system-level mechanical circuit breaker model
    Liu, Siyuan
    Popov, Marjan
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2018, 103 : 159 - 167
  • [7] Development of a Vacuum Circuit Breaker with Breaking and Switching capability
    Kim, Byoung-Chul
    Kim, Sung-Tae
    Ahn, Kil-Young
    Lee, Jong-Ho
    25TH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM (ISDEIV 2012), 2012, : 221 - 223
  • [8] History of vacuum circuit breaker and recent development in Japan
    Homma, M
    Sakaki, M
    Kaneko, E
    Yanabu, S
    ISDEIV: XXITH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM, VOLS 1 AND 2, PROCEEDINGS, 2004, 21 : 378 - 383
  • [9] Investigation on the Interrupting Test of Mechanical HVDC Vacuum Circuit Breaker
    Wang, Yongxing
    Bi, Zeyu
    Zou, Jiyan
    Huang, Zhihui
    Dong, Wenliang
    2017 4TH INTERNATIONAL CONFERENCE ON ELECTRIC POWER EQUIPMENT-SWITCHING TECHNOLOGY (ICEPE-ST), 2017, : 352 - 355
  • [10] Experiment and Simulation Research on Mechanical Characteristic of Vacuum Circuit Breaker
    Duan, Xiaoli
    Wang, Ting
    Ye, Huisheng
    Feng, Dingyu
    Fan, Min
    Xiu, Shixin
    2016 27TH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM (ISDEIV), VOL 2, 2016,