摘要
In order to study aging characteristics of oil-paper insulation in transformer, we performed accelerated aging test of oil-paper insulation sample under 130℃ and measured polarization/depolarization current of samples in different aging stages. Then, taking the steady oil aging charge quantity Qo and steady oil-paper interfacial polarization charge quantity Qo-p were performed as aging characteristics of transformer oil and oil-paper interfacial polarization. And extracted peak value and peak time tpeak of time domain dielectric spectroscopy as aging characteristics of insulation paper. Finally, we verified the feasibility of the above described aging characteristics by field tests. The results show that, Qo increases with sample aging days and there is a linear fitting relationship between them. Qo can represent strength of dipole polarization in oil. Extracted peak value and tpeak can represent the strength and response speed of interfacial polarization in paper caused by cellulose cracking. There is exponential negative correlation between extracted peak value and degree of polymerization. Qo-p increases with sample aging days and there is a linear fit relationship between them. Qo-p can represent strength of oil-paper interface polarization. © 2017, High Voltage Engineering Editorial Department of CEPRI. All right reserved.
引用
收藏
页码:195 / 202
页数:7
相关论文
共 17 条
  • [1] Saha T.K., Review of modern diagnostic techniques for assessing insulation condition in aged transformers, IEEE Transactions on Dielectrics and Electrical Insulation, 10, 5, pp. 903-917, (2003)
  • [2] Wang M., Vandermaar A.J., Srivastava K.D., Review of condition assessment of power transformers in service, IEEE Electrical Insulation Magazine, 18, 6, pp. 12-25, (2002)
  • [3] Eklund P.P., Martins M.A., Insulating paper ageing and furfural formation, Proceedings of 2003 Electrical Insulation Conference and Electrical Manufacturing & Coil Winding Technology Conference, pp. 283-288, (2003)
  • [4] Wei J.L., Zhang G.J., Dong M., Et al., Research progress on insulation condition estimation for oil-immersed power transformer, Proceedings of 2008 International Symposium on Electrical Insulating Materials(ISEIM 2008), pp. 32-35, (2008)
  • [5] Wu G., Duan Z., Cui Y., Et al., Analysis of transient moisture diffusion in oil-paper insulation using polarization and depolarization charge difference model, High Voltage Engineering, 41, 2, pp. 592-601, (2015)
  • [6] Zhou L., Wang L., Li X., Et al., Time domain conductivity model of oil-paper insulation using polarization and depolarization current method, High Voltage Engineering, 40, 5, pp. 1433-1438, (2014)
  • [7] Wei J., Wang S., Peng H., Et al., Investigation of dielectric response characteristics of transformer oil-paper insulation-dielectric spectroscopy of acceleratedly thermal aging, Transactions of China Electrotechnical Society, 27, 5, pp. 56-62, (2012)
  • [8] Liu J., Liao R., Lu Y., Et al., Time domain dielectric characteristics for quantitative assessment of moisture content in transformer oil-paper insulation, Transactions of China Electrotechnical Society, 30, 2, pp. 196-203, (2015)
  • [9] Zhou L.J., Li X.L., Wu G.N., Low frequency dispersion mechanism of dielectric response for oil-paper insulation diagnosis, High Voltage Engineering, 39, 8, pp. 1873-1880, (2013)
  • [10] Saha T.K., Purkait P., Understanding the impacts of moisture and thermal ageing on transformer's insulation by dielectric response and molecular weight measurements, IEEE Transactions on Dielectrics and Electrical Insulation, 15, 2, pp. 568-582, (2008)