Study on the method for translating fire resistance time between standard fire furnace test and compartment fire Part 2: Applicability of MQH formula for compartment fire

被引:0
作者
Mizukami T. [1 ]
Tanaka T. [2 ]
机构
[1] NILIM, 1 Tachihara, Tsukuba-shi, Ibaraki
[2] Emiritus of Kyoto University, Gokasyo, Uji, Kyoto
关键词
Buildings; -; Fires; Furnaces;
D O I
10.11196/kasai.68.1_23
中图分类号
学科分类号
摘要
In performance-based structural fire safety design, various calculation models are used to predict the structural behaviors of building elements exposed to fire. Although many of such calculation models require material properties of building elements as input data, it is often technically and economically difficult to obtain such material properties. A potential alternative is to develop a method to translate the fire resistance time of a building element assessed by existing fire furnace testing to the time for which the element can endure in arbitrary compartment fire conditions. In this paper, we checked and explored the possibility of such a translation method of fire resistance time between fire furnace tests and ventilation controlled compartment fires. It is found that ventilation controlled compartment fires cannot be expressed by a closed form formula, e.g., MQH formula. Instead, we propose a practicable translation method of fire resistance time, in which it is not necessary to know the properties of the building element tested although it is necessary to have the thermal property of compartment boundary. © 2018 Japan Association for Fire Science and Engineering. All rights reserved.
引用
收藏
页码:23 / 33
页数:10
相关论文
共 7 条
[1]  
Ingberg S.H., Tests of Severity of Building Fires, (1928)
[2]  
McCaffrey B.J., Quintiere J.G., Harkleroad M.F., Estimating room temperatures and likelihood of flashover using fire test data correlations, Fire Technology, 17, 2, pp. 98-119, (1981)
[3]  
Fire Resistance Tests-Elements of Building Construction, (1999)
[4]  
Nakaya I., Tanaka T., Yoshida M., Doorway flow induced by a propane fire, Fire Safety Journal, 10, 1986, pp. 185-195
[5]  
Huggett C., Estimation of rate of heat release by means of oxygen consumption method, Fire and Materials, 4, 20, (1980)
[6]  
Kawagoe K., Sekine T., Estimation of fire temperature curve in concrete buildings with different thermal conductivity of wall, Buletin of Japan Association for Fire Science and Engineering, 3, 2, (1954)
[7]  
Sato M., Tanaka T., Wakamatsu T., Simple formula for ventilation - Controlled fire temperature, J. Applied Fire Science, 6, 3, pp. 269-290, (1996)