Coordinate Control of Power Fluctuation Suppression and Current Balance Under Unbalanced Voltage Conditions

被引:0
|
作者
Wang Y. [1 ]
Ou M. [1 ]
Chen Y. [2 ]
Chen Z. [1 ]
Xiao Z. [1 ]
Xu Z. [1 ]
机构
[1] State Grid Hunan Electric Power Corporation Limited Economical & Technical Research Institute, Changsha, 410004, Hunan Province
[2] National Electric Power Conversion and Control Engineering Technology Research Center, Hunan University, Changsha, 410082, Hunan Province
基金
中国国家自然科学基金;
关键词
Coordinate control; Current quality; Grid-connected inverter; Power control; Voltage unbalance;
D O I
10.13334/j.0258-8013.pcsee.162639
中图分类号
学科分类号
摘要
The output power fluctuation and current quality of the grid-connected inverter under the unbalanced voltage environment are opposite to each other. First, the paper deduces the internal connection between the power oscillations and the current quality under unbalanced grid faults, the key factors that affect power fluctuation and current quality were analyzed. Then, a flexible power control strategy in stationary reference frame was proposed, and the power oscillations and the current quality can be controlled flexibly by changing the harmonic components in the output current. The proposed control strategy is convenient to realize without the need for positive/negative sequence extraction calculation, low pass filter or notch filter. Finally, the correctness of the proposed power control strategy is verified by simulation and experiment. © 2017 Chin. Soc. for Elec. Eng.
引用
收藏
页码:6981 / 6987
页数:6
相关论文
共 13 条
  • [1] Zhao Q., Guo X., Wu W., Research on control strategy for single-phase grid-connected inverter, Proceedings of the CSEE, 27, 16, pp. 60-64, (2007)
  • [2] Suh Y., Lipo T.A., Modeling and analysis of instantaneous active and reactive power for PWM AC/DC converter under generalized unbalanced network, IEEE Transactions on Power Delivery, 21, 3, pp. 1530-1540, (2006)
  • [3] Etxeberria-Otadui I., Viscarret U., Caballero M., Et al., New optimized PWM VSC control structures and strategies under unbalanced voltage transients, IEEE Transactions on Industrial Electronics, 54, 5, pp. 2902-2914, (2007)
  • [4] Quan Y., Nian H., Resonance-based sliding mode control of grid connected inverters under unbalanced and harmonic grid voltages, Proceedings of the CSEE, 34, 9, pp. 1345-1352, (2014)
  • [5] Hu J., He Y., Xu L., Et al., Improved control of DFIG systems during network unbalance using PI-R current regulators, IEEE Transactions on Industrial Electronics, 56, 2, pp. 439-451, (2009)
  • [6] Lu Z., Luo A., Rong F., Et al., Micro-grid PQ control strategy analysis under utility voltage imbalance, Power Electronics, 44, 6, pp. 71-74, (2010)
  • [7] Zhou J., Luo A., Chen Y., Et al., Voltage unbalance compensation for low-voltage microgrid with multi parallelly connected inverters, Power System Technology, 38, 2, pp. 412-418, (2014)
  • [8] Wang Y., Luo A., Jin G., An unbalanced voltage compensation method for parallel inverters in microgrids, Proceedings of the CSEE, 35, 19, pp. 4956-4964, (2015)
  • [9] Song H.S., Nam K., Dual current control scheme for PWM converter under unbalanced input voltage conditions, IEEE Transactions on Industrial Electronics, 46, 5, pp. 953-959, (1999)
  • [10] Song H.S., Joo I.W., Nam K., Source voltage sensorless estimation scheme for PWM rectifiers under unbalanced conditions, IEEE Transactions on Industrial Electronics, 50, 6, pp. 1238-1245, (2003)