Grid load security domain based on voltage level constraint

被引:0
作者
Zhu W. [1 ]
Ling C. [1 ]
Zhang Y. [1 ]
Ru L. [2 ]
机构
[1] College of Electrical & Information Engineering, Changsha University of Science& Technology, Changsha, 410114, Hunan Province
[2] State Grid Hengyang Power Supply Company, Hengyang, 421000, Hunan Province
来源
Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering | 2016年 / 36卷 / 23期
关键词
Load security domain; Load security domain matching; Ratio adjustment; Reactive power compensation; Voltage level constraint;
D O I
10.13334/j.0258-8013.pcsee.160429
中图分类号
学科分类号
摘要
Voltage stability limits will vary with running states, and far below the normal safety level. Therefore, the analysis of node load security domains based on voltage security level constraints so that the load of each node and reactive power compensation are limited to the region, to maintain grid voltage security, will be more meaningful. The analysis based on Thevenin equivalent model found the load security domains are existed indeed. So, based on line models, the parameters and the rated voltages, the load security domains of both ends of lines had been analyzed to get, that were, enclosed by eccentric arc and P and Q positive axis. By matching of the security domains on both sides of transformers, the load security domains of each node in grid had been obtained; by adjusting the ratio, adjustable the load security domains at the line ends of low-voltage side; reactive power compensation was deemed load adjusted to accommodate the load security domains at the line end of high-voltage side. Case studied to verify the feasibility of load security domain analysis. The study has practical significance distribution grid operation and reactive planning. © 2016 Chin. Soc. for Elec. Eng.
引用
收藏
页码:6389 / 6400
页数:11
相关论文
共 26 条
[1]  
Gregor V., A new concept of voltage-clapse protection based on local phasors, IEEE Transactions on Power Delivery, 19, 2, pp. 576-581, (2004)
[2]  
Guo R., Han Z., An improved zero eigen value method for point of collapse, Proceedings of the CSEE, 20, 5, pp. 63-66, (2000)
[3]  
Kunder P., Power System Stability And Control, pp. 647-653, (2002)
[4]  
Taylor, Power System Voltage Stability, pp. 18-27, (2002)
[5]  
He Y., Liu G., Gao L., Improved continuation method with controlled step size for the solution of voltage stability bifurcation, Proceedings of the CSU-EPSA, 24, 5, pp. 112-116, (2012)
[6]  
Luo H., Wu Z., Dai Q., Et al., Fast computation of Thevenin equivalent parameters, Proceedings of the CSEE, 29, 1, pp. 35-39, (2009)
[7]  
Ivan S., Gregor V., Ferdinand G., Local voltage-stability index using Tellegen's theorem, IEEE Transactions on Power Systems, 21, 3, pp. 1267-11275, (2006)
[8]  
Tang Y., Sun H., Yi J., Et al., Tracing algorithm for Thevenin equivalent parameters based on complete differential equation, Proceedings of the CSEE, 29, 13, pp. 48-53, (2009)
[9]  
Zhu W., Tang R., Correction of the Thevenin parameters based on local measurement information, Journal of Electric Power Science and Technology, 27, 2, pp. 47-51, (2012)
[10]  
Hang N., Liao Q., Li R., Et al., A flexible node algorithm for critical voltage collapse power flow in power system, Proceedings of the CSEE, 25, 17, pp. 60-64, (2005)