Study on lightning protection measures for distribution lines and customer equipment against back flow lightning current from radio communication station

被引:0
|
作者
Ishimoto K. [1 ]
Asakawa A. [1 ]
Sato T. [2 ]
Miyama Y. [3 ]
机构
[1] Electric Power Engineering Research Laboratory, CRIEPI, 2-6-1, Nagasaka, Yokosuka
[2] Tohoku Electric Power Co., Inc., 1-7-1, Honcho, Aoba-ku, Sendai
[3] Shoden Co., Ltd., 365, Sanno-cho, Inage-ku, 263-0002, Chiba
来源
Ishimoto, Kazuyuki (ishimoto@criepi.denken.or.jp) | 1600年 / Institute of Electrical Engineers of Japan卷 / 136期
关键词
Back flow lightning current; Communication tower; Customer equipment; Distribution lines; Lightning protection measures;
D O I
10.1541/ieejpes.136.584
中图分类号
学科分类号
摘要
Recently, with the expansion of communication network areas, the number of radio communication stations, built in the neighborhood of customer houses, has increased. If lightning strikes a communication radio tower, part of the lightning current flows into the distribution line and into customer houses. This may cause the failure of distribution lines or customer equipment. To protect distribution lines and customer equipment from lightning faults, it is necessary to analyze the surge phenomena in distribution lines and customer equipment and take appropriate protection measures. In this study, we examined the effect of lightning protection measures for distribution lines and customer equipment against lightning strikes to a communication tower. First, using an actual-scale test distribution line, we measured the lightning current flowing into distribution lines and customer equipment. Secondly, we quantitatively examined the effect of lightning protection measures by lighting surge analysis while changing each parameter. From the experimental and analytical results, we show that the proposed protection measures can reduce the lightning current flowing into distribution lines and customer equipment. © 2016 The Institute of Electrical Engineers of Japan.
引用
收藏
页码:584 / 595
页数:11
相关论文
共 43 条
  • [31] Effect of Grounding Resistance Connected to Surge Arresters in Power Distribution Lines on Lightning Surge Behavior Observed in Customer's Equipment
    Hidaka, Tetsuya
    Shiota, Katsushi
    Ishimoto, Kazuyuki
    Asakawa, Akira
    ELECTRICAL ENGINEERING IN JAPAN, 2016, 195 (02) : 1 - 10
  • [32] Transient Grounding Characteristic of Wind Turbines Affecting Back-flow Lightning Current into Distribution System
    Yamamoto, Kazuo
    Kubo, Yuki
    Sumi, Shinichi
    2016 33RD INTERNATIONAL CONFERENCE ON LIGHTNING PROTECTION (ICLP), 2016,
  • [33] An Analytical Study on Effective Lightning Protection Measures for Pole-Mounted Distribution Transformers on Terminal Poles
    Kanatani, Kenichi
    Matsuura, Susumu
    Michishita, Koji
    IEEJ TRANSACTIONS ON ELECTRICAL AND ELECTRONIC ENGINEERING, 2023, 18 (11) : 1845 - 1852
  • [34] Study on Power Frequency Follow Current Interruption Test of Self Arc-extinguishing Lightning Protection Gap in 35 kV Distribution Lines
    Wang J.
    Huang S.
    Han L.
    Yan R.
    Xu Y.
    Dianwang Jishu/Power System Technology, 2021, 45 (03): : 1208 - 1213
  • [35] Study on Potential Distribution of Lightning Protection Insulator and Measures Improving Electric Field Uniformity Under Ice Coating
    Wu W.
    Jiang Z.
    Wang B.
    Hu J.
    Xie P.
    Peng Y.
    Dianwang Jishu/Power System Technology, 2019, 43 (11): : 4225 - 4230
  • [36] Modelling of grounding systems for better protection of communication installations against effects from electric power system and lightning
    Grcev, L
    INTELEC 2001: TWENTY-THIRD INTERNATIONAL TELECOMMUNICATIONS ENERGY CONFERENCE, 2001, (484): : 461 - 468
  • [37] Preliminary Assessment of Protection of Distribution Lines Against Direct Lightning Strokes Through Multi-chamber Arresters and Shield Wires
    Stracqualursi, Erika
    Araneo, Rodolfo
    Andreotti, Amedeo
    2022 IEEE INTERNATIONAL CONFERENCE ON ENVIRONMENT AND ELECTRICAL ENGINEERING AND 2022 IEEE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS EUROPE (EEEIC / I&CPS EUROPE), 2022,
  • [38] An experimental study of the effect of SPDs on protection for home electric appliances against lightning surges through a distribution line
    Aiba, Kiyoshi
    Okabe, Shigemitsu
    Miyazald, Teru
    Yoshikawa, Masahide
    IEEJ Transactions on Power and Energy, 2007, 127 (04) : 581 - 588
  • [39] 110- to 330-kV substation surge protection against lightning surge coming from transmission lines
    N. A. Mufid-Zade
    H. Houassine
    S. M. Tagi-Zade
    Russian Electrical Engineering, 2012, 83 (8) : 447 - 452
  • [40] Analysis of current distribution among long-flashover arresters for 10 kV overhead line protection against direct lightning strikes
    Belko, D. O.
    Podporkin, G. V.
    2016 33RD INTERNATIONAL CONFERENCE ON LIGHTNING PROTECTION (ICLP), 2016,