Characteristic analysis on vacuum interrupter with cup-typed AMF contacts during the forcing current to zero process

被引:0
作者
Zheng, Zhanfeng [1 ]
Dong, Enyuan [1 ]
Zou, Jiyan [1 ]
Lou, Yan [1 ]
Zhang, Zhenwei [1 ]
Qi, Guanqiu [1 ]
Qin, Taotao [1 ]
机构
[1] Dept. of Electrical Engineering, Dalian University of Technology
来源
Journal of Computational Information Systems | 2013年 / 9卷 / 19期
关键词
Axial magnetic field (AMF); DC interruption; Force current to Zero; Vacuum arc;
D O I
10.12733/jcis7030
中图分类号
学科分类号
摘要
The vacuum switch with the cup-typed axial magnetic field contacts, of which the advantages are such as lower arc voltage, less contact erosion, large breaking capacity, smaller size, and so on, is widely applied in the AC power system. To utilize it for the DC interruption, this paper analyzed the characteristics of vacuum interrupter with cup-typed axial magnetic field contacts during the DC fault current forced to zero process by using finite element method. The conclusions were obtained as follows: 1) the magnetic flux density in the axial direction (Bz) presents consistency along with the longitudinal direction in gap space, and the largest phase delay in the center of transverse section. 2) After the starting of the arc burning, Bz has an approximately 1-1.5 ms phase delay at first, later is growing proportionally to the fault current increasing rate. 3) As increasing the frequency of the superposed reversed current, the phase delay of Bz is intensified, which result in the value of Bz around the first current zero being very close to the one at the moment of beginning commutation, and it is adverse to the breaking current. © 2013 Binary Information Press.
引用
收藏
页码:7849 / 7856
页数:7
相关论文
共 12 条
  • [1] Fink H., Heimbach M., Shang W., Vacuum interrupters with axial magnetic field contacts, ABB Review, 1, pp. 60-64, (2001)
  • [2] Zheng Z., Zou J., Dong E., Et al., DC interruption and DC circuit breaker, High Voltage Apparatus, 42, 6, pp. 445-449, (2006)
  • [3] Luo Y., Duan X., Tian Z., Status monitoring and digital communication of the intelligent vacuum circuit breaker in smart grid, Journal of Computational Information Systems, 8, 21, pp. 8707-8715, (2012)
  • [4] Huang Z., Duan X., Zou J., Et al., Research on fault inception detection for controlled fault interruption, Journal of Computational Information Systems, 8, 9, pp. 3851-3858, (2012)
  • [5] Xiang C., Zou J., Liao M., Et al., Experimental and simulated researches on vacuum arc in short gap, Journal of Computational Information Systems, 8, 11, pp. 4553-4560, (2012)
  • [6] Cheng X., Duan X., Liao M., Et al., Simulation study on interaction between vacuum switch and SF<sub>6</sub> switch in the high-current interruption process, Journal of Computational Information Systems, 8, 11, pp. 4735-4742, (2012)
  • [7] Paul B.-J., Calculation of eddy-current-induced magnetic fields in vacuum interrupters with axial magnetic field contacts, IEEE Transactions on Magnetics, 24, 5, pp. 2204-2214, (1988)
  • [8] Stoving P.N., Fred Bestel E., Finite element analysis of AMF vacuum contacts, XVIIIth International Symposium on Discharges and Electrical Insulation in Vacuum, (1998)
  • [9] Fink H., Heimbach M., Shang W., Vacuum interrupters with axial magnetic field contacts based on bipolar and quadrupolar design, XIXth International Symposium on Discharges and Electrical Insulation in Vacuum, (2000)
  • [10] Shi Z., Jia S., Fu J., Et al., Analysis of electrode for vacuum interrupters with nonuniform axial magnetic field, International Conference on Power System Technology, (2002)