Ten differences of seasonal borehole thermal energy storage system from ground-source heat pump system

被引:2
作者
Zhao, Xingwang [1 ,2 ]
Li, Yanwei [1 ]
Chen, Xin [1 ]
Yin, Yonggao [1 ,2 ]
机构
[1] Southeast Univ, Sch Energy & Environm, Nanjing 210096, Peoples R China
[2] Minist Educ, Engn Res Ctr Bldg Equipment Energy & Environm, Beijing, Peoples R China
基金
中国博士后科学基金; 中国国家自然科学基金;
关键词
Borehole thermal energy storage; Seasonal thermal energy storage; Ground-source heat pump system; Peak shifting and valley filling; Clean energy; Zero carbon heating; SENSITIVITY-ANALYSIS; PERFORMANCE PREDICTION; NEURAL-NETWORKS; OPERATION; OPTIMIZATION; DESIGN; PHASE; TECHNOLOGIES; TANK;
D O I
10.1016/j.enbuild.2024.114994
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Since both the cross-seasonal borehole thermal energy storage (BTES) system and the ground source heat pump (GSHP) system use buried tubes for heat exchange, GSHP is often mistaken for a BTES system. However, there are essential differences between the GSHP system and the BTES system, and the purpose of this study is to elucidate in detail the differences between these two systems. This study first summarizes the practical application cases of seasonal BTES globally, and then deeply compares and analyzes the differences between the seasonal BTES system and GSHP system from ten different perspectives, including system definition, technology timeline, purpose of buried tube heat exchanger, heat sources, soil temperature changes, buried tube heat exchanger volume, design of the buried tube heat exchanger, energy storage modes, biggest drawback, system performance evaluation. Finally, the future development prospects and research directions of the seasonal BTES system are further discussed. In summary, although the GSHP system may be confused with the seasonal BTES system in some aspects, they are indeed two different systems. Compared to the GSHP system, the seasonal BTES system can solve the contradiction between energy supply and demand in time and space, and effectively improve energy utilization efficiency.
引用
收藏
页数:18
相关论文
共 148 条
[1]   Experimental investigation of underground seasonal cold energy storage using borehole heat exchangers based on laboratory scale sandbox [J].
Abbas, Zulkarnain ;
Chen, Dongwen ;
Li, Y. ;
Yong, Li ;
Wang, R. Z. .
GEOTHERMICS, 2020, 87
[2]   Improving the energy efficiency of ground-source heat pump systems in heating dominated school buildings: A case study in Belgium [J].
Allaerts, K. ;
Al Koussa, J. ;
Desmedt, J. ;
Salenbien, R. .
ENERGY AND BUILDINGS, 2017, 138 :559-568
[3]  
[Anonymous], 2016, TASK 45 / 55: Guidelines on How to Design Seasonal Storage
[4]  
[Anonymous], GROUND SOURCE HEAT P
[5]  
Arabkoohsar A., 2023, Future Grid-Scale Energy Storage Solutions
[6]   Temperature distributions in pavement and bridge slabs heated by using vertical ground-source heat pump systems [J].
Balbay, Asim ;
Esen, Mehmet .
ACTA SCIENTIARUM-TECHNOLOGY, 2013, 35 (04) :677-685
[7]  
Balbay A, 2010, SCI RES ESSAYS, V5, P3955
[8]  
Baser Tugce, 2015, IFCEE 2015. International Foundations Congress and Equipment Expo 2015. Proceedings, P1608
[9]  
Baudoin A., 1988, Stockage intersaisonnier de chaleur dans le sol par batterie d'echangeurs baionnette verticaux
[10]  
modele de predimensionnement