Influence of Different PLLs on Stability of LCC-HVDC Control Loop

被引:0
|
作者
Liu J. [1 ]
Wang J. [1 ]
Ye Y. [2 ]
Wang Z. [1 ]
机构
[1] School of Electric Power, South China University of Technology, Guangdong Province, Guangzhou
[2] Guangzhou Power Supply Bureau, Guangdong Power Grid Limited Liability Company, Guangdong Province, Guangzhou
来源
基金
中国国家自然科学基金;
关键词
high voltage direct current (HVDC) transmission; phase locked loop; small interference dynamic model; stability margin;
D O I
10.13335/j.1000-3673.pst.2023.0121
中图分类号
学科分类号
摘要
In this paper, the influence of PI parameter changes of the phase-locked loop control loop on the stability margin of the DC control loop when different phase-locked loops are used on the inverter side of in the line commutated converter high voltage direct current (LCC-HVDC) system is studied. Firstly, the LCC-HVDC small interference dynamic model using the moving average filter (MAF) and the cascaded delayed signal cancellation (CDSC) of the inverter side phase-locked loop is established, and then the correctness of the small interference dynamic model is verified by electromagnetic transient simulation. Secondly, based on the Laplace transform, the transfer function of the constant voltage control loop of the system is obtained, and the influence of different phase-locked loops on the stability of the constant voltage control loop is evaluated from the stability margin index. The simulation results verify the correctness of the theoretical analysis results. Finally, the relevant verification is carried out on the engineering model to illustrate the generality of the conclusions in this paper. © 2024 Power System Technology Press. All rights reserved.
引用
收藏
页码:1202 / 1213
页数:11
相关论文
共 21 条
  • [1] (2011)
  • [2] LU Pengfei, Research on HVDC Operation Characteristics Under Influence of Hybrid AC/DC Power Grids[J], Power System Technology, 46, 2, pp. 492-502, (2022)
  • [3] QIU Zhiyuan, LI Daoyu, FENG Wenxin, Design of intelligent management assistant system for setting value of HVDC control and protection[J], Electronic Design Engineering, 30, 14, pp. 44-47, (2022)
  • [4] GOLESTAN S, GUERRERO J M, Conventional synchronous reference frame phase-locked loop is an adaptive complex filter[J], IEEE Transactions on Industrial Electronics, 62, 3, pp. 1679-1682, (2015)
  • [5] SONG Jinzhao, LI Yongli, ZENG Liang, Review on commutation failure of HVDC transmission system[J], Automation of Electric Power Systems, 44, 22, pp. 2-13, (2020)
  • [6] HUANG Jianming, WU Chunhua, Phase Detection of fundamental positive sequence voltage based on sequence-decoupled resonant controller.power system technology, 37, 3, pp. 667-672, (2013)
  • [7] GONG Yingming, WANG Juanjuan, WANG Zimin, A novel phase-locked loop for HVDC[J], Power System Technology, 43, 11, pp. 4097-4104, (2019)
  • [8] JIANG Zijian, YANG Huan, SHEN Jianhui, DSTATCOM control strategy based on cascaded delayed signal cancellation-phase locked loop algorithm[J], Power System Technology, 39, 7, pp. 1989-1994, (2015)
  • [9] YAN Peilei, GE Xinglai, WANG Huimin, PLL Parameter optimization design for renewable energy grid-connected inverters in weak grid[J], Power System Technology, 46, 6, pp. 2210-2221, (2022)
  • [10] LIU Jingjia, LI Huan, YU Hualong, Characteristics comparison of different phase-locked loops in HVDC power transmission systems[J], Southern Power System Technology, 15, 8, pp. 12-21, (2021)