High-resistance grounding fault detector by use of feeding current

被引:0
作者
Hase, Shin-Ichi [1 ]
Okui, Akinobu [1 ]
Sekijima, Shiro [2 ]
Sugai, Shunichi [2 ]
Akagi, Masataka [2 ]
Kimura, Takashi [3 ]
机构
[1] Power Supply Technology Division
[2] East Japan Railway Company
[3] Shikoku Railway Company
来源
Quarterly Report of RTRI (Railway Technical Research Institute) (Japan) | 2008年 / 49卷 / 02期
关键词
DC electric railways; Feeding current; High-resistance grounding fault; Protection;
D O I
10.2219/rtriqr.49.108
中图分类号
学科分类号
摘要
The detection of high-resistance grounding faults in DC electric railways is difficult due to the impossibility of distinguishing fault current from load current in such systems. We therefore propose a new detection method to distinguish fault current from load current using the total feeding current of two substations. The technique takes advantage of the fact that the average load current is different from the average fault current. First, this paper describes the new method of detecting high-resistance grounding faults by using the total feeding current, then evaluates the length of time required for detection by simulation and shows the experimental results.
引用
收藏
页码:108 / 112
页数:4
相关论文
共 2 条
  • [1] Kimura T., Sugai S., Okui A., Hase S., Development of the DC Ground Fault Detection System Using the Total Current of Two Substations, The 2007 Japan Industry Applications Society Conference, pp. 3-40, (2007)
  • [2] Hase S., Okui A., Sekijima S., Sugai S., Akagi M., Kimura T., Development of High resistance Grounding Fault Detector by Making Use of Load Current,, RTRI Report