An AGC control performance index for main tie-lines in interconnected power grids

被引:5
作者
机构
[1] State Key Laboratory of Advanced Electromagnetic Engineering and Technology, Huazhong University of Science and Technology
来源
Wen, J. (jinyu.wen@hust.edu.cn) | 1600年 / Automation of Electric Power Systems Press卷 / 37期
关键词
Automatic generation control (AGC); Control performance standard (CPS); Multi-zone; Multi-zone tie-line index (index MT); Standard T; Ultra-high voltage (UHV) synchronized power grid;
D O I
10.7500/AEPS201212227
中图分类号
学科分类号
摘要
With the stochastic power fluctuation occurring on the ultra-high voltage (UHV) AC tie-line of North China power grid and Central China power grid, a control performance index, namely the multi-zone tie-line index (MT index) is proposed. The index is a combination of the basic ideas of both NERC's control performance standard (CPS) and standard T. This index focuses on the automatic generation control (AGC) of UHV tie-lines of interconnected power grids. It can be used to evaluate the subarea's contribution (e.g. provincial power grids) to the control of power fluctuation on the main tie-line in a large power grid. Based on this, an AGC controller for suppressing the power fluctuation on main tie-lines is designed. Simulation results show that controllers designed under MT index can be used to suppress the power fluctuation on main tie-lines efficiently. ©2013 State Grid Electric Power Research Institute Press.
引用
收藏
页码:111 / 117
页数:6
相关论文
共 13 条
[11]  
Jaleeli N., Vanslyck L.S., Control performance standards and procedures for interconnected operation, (1997)
[12]  
Liu R., Lin W., Li W., Et al., Discussion on the control performance assessment criteria for interconnected power systems, Automation of Electric Power Systems, 29, 8, pp. 87-91, (2005)
[13]  
Yao M., Shoults R.R., Kelm R., AGC logic based on NERC's new control performance standard and disturbance control standard, IEEE Trans on Power Systems, 15, 2, pp. 852-857, (2000)