Impacts of contamination and hydrophobicity level on the leakage currents of composite insulators

被引:0
作者
机构
[1] State Key Laboratory of Power Transmission Equipment and System Security and New Technology, Chongqing University
来源
Jiang, X. (xljiang@cqu.edu.cn) | 1600年 / Science Press卷 / 39期
关键词
Composite insulator; Contamination; Hydrophobicity; Leakage current; Temporal and frequency characteristics; Transmission lines;
D O I
10.3969/j.issn.1003-6520.2013.11.001
中图分类号
学科分类号
摘要
For composite insulators, analyzing the relationships between leakage current and contamination/hydrophobicity level could be considered as an effective measure for forecasting pollution flashovers. Therefore, using experimental data in artificial climate laboratory, we simulated the impacts of contamination and hydrophobicity level on leakage current to reveal the relationships between them. The results show that, with the increase of contamination, the maximum effective value of leakage current and the number of high-amplitude pulses increase, the difference between phases of leakage current and applied voltage decreases from -33.19° to 0, and the fundamental harmonic content of leakage current decreases from 98.03% to 79.89% while the other harmonic contents increase. With the decrease of hydrophobicity, the maximum effective value of leakage current and the number of high-amplitude pulses increase, the difference between phases of leakage current and applied voltage decreases, and the fundamental harmonic content of leakage current decreases from 97.56% to 85.97% while the other harmonic contents increase.
引用
收藏
页码:2573 / 2580
页数:7
相关论文
共 27 条
  • [1] Mackevich J., Shah M., Polymer outdoor insulating materials. part I: comparison of porcelain and polymer electrical insulation, IEEE Electrical Insulation Magazine, 13, 3, pp. 5-12, (1997)
  • [2] Fernando M.A.R.M., Gubanski S.M., Leakage currents on non-ceramic insulators and materials, IEEE Transactions on Dielectrics and Electrical Insulation, 6, 5, pp. 660-667, (1999)
  • [3] Insulation pollution monitoring, International Council on Large Electric Systems (CIGRE), pp. 79-89, (1994)
  • [4] Vazquez R.I., Chavez F.J.L., Criteria for the diagnostic of polluted ceramic insulators based on the leakage current monitoring technique, Conference on Electrical Insulation and Dielectric Phenomena, pp. 102-111, (1999)
  • [5] Marungsri B., Shinokubo H., Matsuoka R., Et al., Effect of specimen configuration on deterioration of silicone rubber for polymer insulators in salt fog ageing test, IEEE Transactions on Dielectrics and Electrical Insulation, 13, 1, pp. 129-138, (2006)
  • [6] Devendranath D., Channakeshava, Rajkumar A.D., Leakage current and charge in RTV coated insulators under pollution conditions, IEEE Transactions on Dielectrics and Electrical Insulation, 9, 2, pp. 294-299, (2002)
  • [7] Sun C.X., Li J.Y., Contamination level prediction of insulators based on the characteristics of leakage current, IEEE Transactions on Power Delivery, 25, 1, pp. 417-424, (2010)
  • [8] Suda T., Frequency characteristics of leakage current waveforms of an artificially polluted suspension insulator, IEEE Transactions on Dielectrics and Electrical Insulation, 8, 4, pp. 705-710, (2001)
  • [9] Suda T., Member S., Frequency characteristics of leakage current waveforms of a string of suspension insulators, IEEE Transactions on Power Delivery, 20, 1, pp. 481-488, (2005)
  • [10] Li J.Y., Sun C.D., Sebo S.T., Humidity and contamination severity impact on the leakage currents of porcelain insulators, IET Transactions on Generation, Transmission and Distribution, 5, 1, pp. 19-28, (2009)