Control Strategy for operating flexibility of coal-fired power plants in alternate electrical power systems

被引:0
作者
Liu, Jizhen [1 ]
Zeng, Deliang [1 ]
Tian, Liang [1 ]
Gao, Mingming [1 ]
Wang, Wei [1 ]
Niu, Yuguang [1 ]
Fang, Fang [1 ]
机构
[1] State Key Laboratory of Alternate Electrical Power System With Renewable Energy Sources (North China Electric Power University), Changping District, Beijing
来源
Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering | 2015年 / 35卷 / 21期
关键词
Alternate electrical power system; Coal-fired power plants; Cold source throttling; Condensate throttling; Flexibility; Low-load operation;
D O I
10.13334/j.0258-8013.pcsee.2015.21.001
中图分类号
学科分类号
摘要
To improve the operating flexibility of coal fired units is an effective and necessary way for our country and even the world to solve the problem of large-scale renewable energy integration in grid. Five key strategies including the condensate throttling, cold source throttling, extraction steam adjustment of heating units, optimal load dispatch in power plants, and wide-range load operation of circulating fluidized bed (CFB) units, were given and introduced exquisitely. The static and dynamic models for the condensate throttling and cold source throttling were set up, which had enough accuracy to be directly used for the design of control system and strategy. The combination coordinated control with condensate throttling or cold source throttling was designed, which can greatly reduce the stepping out time from the load change dead zone, and accelerate the load change speed. © 2015 Chinese Society for Electrical Engineering.
引用
收藏
页码:5385 / 5394
页数:9
相关论文
共 35 条
  • [1] Schiffer H.W., Flexible operation of coal-fired power plants in Germany under the renewable energy background, Cornerstone, 2, 4, pp. 26-31, (2014)
  • [2] Cochran J., Lew D., Kumar N., Improve the flexibility of coal-fired power plants: from the baseload power to the peakshaving power, Cornerstone, 2, 4, pp. 49-53, (2014)
  • [3] Liu J., Basic issues of the utilization of large-scale renewable power with high security and efficiency, Proceedings of the CSEE, 33, 16, pp. 1-8, (2013)
  • [4] Zhang S., Zhou H., Huang Y., Et al., Simulation on A load control system of thermal power units based on the feedback signal of radiant energy, Proceedings of the CSEE, 21, 2, pp. 85-88, (2001)
  • [5] Wang S., Yang H., Li Y., Research on neural network PID optimization and simulation of coordinated control system, Proceedings of the CSEE, 27, 35, pp. 96-101, (2008)
  • [6] Chen Y., Liu J., Tan W., Et al., A fuzzy multi-model control and simulation of coordinated control system for 500mw boiler-turbine unit, Proceedings of the CSEE, 23, 10, pp. 199-203, (2003)
  • [7] Huang H., Wu L., Han J., Et al., A study of active disturbance rejection control on unit coordinated control system in thermal power plant, Proceedings of the CSEE, 24, 10, pp. 168-173, (2004)
  • [8] Yu D.R., Xu Z.Q., Nonlinear coordinated control of drum boiler power unit based on feedback linearization, IEEE Transactions on Energy Conversion, 20, 1, pp. 204-210, (2005)
  • [9] Sun Y., Study on predictive control applied to coordinated control system in the units, (2011)
  • [10] Cheng L., Analysis and research on coordinated control system of boiler-turbine unit based on internal model adaptive control algorithm, (2011)