Auto-reclosing adaptive to distribution line non-communication protection

被引:0
|
作者
Liu, Kun [1 ]
Dong, Xinzhou [1 ]
Shi, Shenxing [1 ]
Wang, Bin [1 ]
机构
[1] State Key Laboratory of Control and Simulation of Power System and Generation Equipments, Department of Electric Engineering, Tsinghua University, Beijing 100084, China
关键词
Electric power system protection - Outages;
D O I
暂无
中图分类号
TM7 [输配电工程、电力网及电力系统];
学科分类号
080802 ;
摘要
Auto-reclosing is an effective method to improve power system reliability. However, the distribution line non-communication protection cannot be easily coordinated with the auto-reclosing, so auto-reclosing has never been applied to series of distribution line non-communication protection systems since bad timing may induce long power failures for some loads. This paper presents an auto-reclosing scheme that adapts to the distribution line non-communication protection. Auto-reclosing is not effective in the load side circuit breaker because this would hinder downstream loads from regaining their power supply after the reserve power source automatically reconnects, so auto-reclosing is applied in the source side circuit breaker. This scheme can restore the power supply to all loads after a temperary fault and minimize the power failure time. The electro-magnetic transient program (EMTP) simulations show the effectiveness of the scheme.
引用
收藏
页码:356 / 361
相关论文
共 50 条
  • [31] Application of Auto-Reclosing Residual Current Device in Lightning Protection for Communications Power Supply
    Liu, Yucheng
    Chen, Rongbin
    2017 IEEE 5TH INTERNATIONAL SYMPOSIUM ON ELECTROMAGNETIC COMPATIBILITY (EMC-BEIJING), 2017,
  • [32] Robust non-communication line protection scheme using novel quantities
    Darwish, Hatem A.
    Kawady, Tamer A.
    Taalab, Abdel-Maksoud I.
    Malik, O. P.
    2006 POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1-9, 2006, : 3246 - +
  • [33] An efficient deep learning based scheme for adaptive auto-reclosing in power transmission lines
    Aloghareh, Farhad Hatami
    Shams, Mohammadreza
    Jannati, Mohsen
    ALEXANDRIA ENGINEERING JOURNAL, 2024, 102 : 327 - 338
  • [34] Adaptive Overhead Transmission Lines Auto-Reclosing Based on Hilbert-Huang Transform
    Baayeh, Arman Ghaderi
    Bayati, Navid
    ENERGIES, 2020, 13 (20)
  • [35] Adaptive Comprehensive Auto-Reclosing Scheme for Shunt Reactor-Compensated Transmission Lines
    Xie, Chao
    Li, Fengting
    IEEE TRANSACTIONS ON POWER DELIVERY, 2020, 35 (05) : 2149 - 2158
  • [36] Adaptive Single-Phase Auto-Reclosing Approach for Shunt Compensated Transmission Lines
    Ahmadi, Seyed-Alireza
    Sanaye-Pasand, Majid
    Jafarian, Peyman
    Mehrjerdi, Hasan
    IEEE TRANSACTIONS ON POWER DELIVERY, 2021, 36 (03) : 1360 - 1369
  • [37] Non-communication protection of distribution feeders with tapped-off-loads
    Bo, ZQ
    Dong, XZ
    Liu, JK
    Shi, SX
    Caunce, BRJ
    Montjean, D
    POWERCON 2002: INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY, VOLS 1-4, PROCEEDINGS, 2002, : 285 - 289
  • [38] A Study on Auto-reclosing Strategy for large-scale wind farm transmission line
    Yuan, Bo
    Zhang, Baohui
    Hao, Zhiguo
    Zhang, Jinhua
    Wang, Xiaoli
    Bo, Zhiqian
    2014 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON), 2014,
  • [39] Implementation of non-communication protection of feeder
    Shi, Shenxing
    Dong, Xinzhou
    Bo, ZhiQian
    Caunce, B.
    Millar, R.
    Dianli Xitong Zidonghue/Automation of Electric Power Systems, 2002, 26 (12): : 45 - 47
  • [40] Research on non-communication protection of distribution lines based on fault components
    Bi, JG
    Dong, XZ
    Guo, YJ
    Bo, ZQ
    POWERCON 2002: INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY, VOLS 1-4, PROCEEDINGS, 2002, : 1151 - 1155