The correlation evaluation through furan analysis of life-time for 22.9kv oil-immersed transformer

被引:0
作者
Kim Y.-S. [1 ]
Hwang M. [1 ]
Jo G.-R. [1 ]
机构
[1] Electrical Safety Research Institute, Korea Electrical Safety Corporation
来源
Kim, Young-Seok (athens9@kesco.or.kr) | 1759年 / Korean Institute of Electrical Engineers卷 / 70期
关键词
Acceleration deterioration; Furan; Insulation paper; Life-time; Oil-immersed transformer;
D O I
10.5370/KIEE.2021.70.11.1759
中图分类号
学科分类号
摘要
To prevent accidents through maintenance and appropriate replacement of oil-immersed transformer, the correlation between the life-time of the transformer was estimated by comparing the furan analysis of the insulation paper according to the accelerated deterioration and the insulating oil. According to accelerated deterioration, the furan value of DDP was reduced to about 1/1000 compared to that of Kraft paper, and it was shown that the thermal properties were excellent by the epoxy coating. As a result of the analysis of the degree of polymerization of the insulating paper, when the furan value was about 200 ppb, it was determined that the paper performance was lowered. Although the number of transformers collected is small, the life-time of the oil-immersed transformer is about 37 years. © 2021 Korean Institute of Electrical Engineers. All rights reserved.
引用
收藏
页码:1759 / 1764
页数:5
相关论文
共 11 条
[1]  
A Statistical Analysis on the Electrical Accident, (2018)
[2]  
Okabe S., Kaneko S., Kohtoh M., Amimoto T., Analysis results for insulating oil components in field transformers, IEEE Transactions on Dielectrics and Electrical Insulation, 17, pp. 302-311, (2010)
[3]  
Cheim Luiz, Platts Donald, Prevost Thomas, Xu Shuzhen, Furan Analysis for Liquid Power Transformers, IEEE Electrical Insulation Magazine, 28, 2, pp. 8-21, (2012)
[4]  
Son Hyeongwook, Kim Woobin, Lee Dongzoon, Kim Jeongtae, The analysis for the correlation between the creepage discharge of transformer pressboard and theamount of dissolved gases in the oil and the furanic products, The transactions of The KIEE, 68, 6, pp. 733-728, (2019)
[5]  
De Pablo A., Pahlavanpour B., Furanic compounds analysis: A tool for predictive maintenance of oil-filled electrical equipment, Electra, 175, pp. 9-31, (1997)
[6]  
Sans J.R., Bilgin K.M., Kelly J.J., Large-scale survey of furanic compounds in operating transformers and implications for estimating service life, IEEE International Symposium on Electrical Insulation, pp. 543-553, (1998)
[7]  
IEEE Guide for Loading Mineral Oil Immersed Transformer, (1995)
[8]  
Standard Test Method for Furanic Compounds in Electrical Insulating Liquids by High-Performance Liquid Chromatography(HPLC), (2015)
[9]  
Mineral insulating oils-Methods for the determination of 2-furfural and related compounds, (1993)
[10]  