Series-parallel Resonance Analysis of Multi-inverter System Based on Modal Analysis

被引:1
|
作者
Li Q. [1 ]
Sun P. [1 ]
Dong G. [2 ]
Chen Y. [2 ]
机构
[1] State Key Laboratory of Power Transmission Equipment Technology, Chongqing University, Shapingba District, Chongqing
[2] State Grid Chongqing Electric Power Research Institute, Yubei District, Chongqing
来源
Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering | 2024年 / 44卷 / 13期
关键词
modal analysis; multi-inverter; resonance identification; resonance type; series-parallel resonance;
D O I
10.13334/j.0258-8013.pcsee.230450
中图分类号
学科分类号
摘要
The resonance analysis method based on modal analysis can obtain accurate resonance positioning of a multi-inverter system, but it has shortcomings in the identification of resonance types. In this paper, a resonance identification method based on modal analysis and participation factor calculation is proposed for multi-inverter systems. A Norton equivalent model of the inverter with active damping of the capacitance current is established and the line impedance is considered. The result difference between series and parallel resonance modal analysis is analyzed when the inverter combination changes. The characteristics of different types of resonances are obtained by classifying the resonance types. A specific modal analysis method is selected for each type of resonance, and the type of resonance is identified by the performance of the participation factor. Finally, a simulation circuit model and an experimental platform are built to verify the correctness of the conclusions. © 2024 Chinese Society for Electrical Engineering. All rights reserved.
引用
收藏
页码:5269 / 5280
页数:11
相关论文
共 28 条
  • [1] YANG Shengchun, XIANG Kelin, YANG Fan, Current situation and prospect of solar thermal power generation industry in China[J], Sino-Global Energy, 22, 6, pp. 19-23, (2017)
  • [2] WANG Yanbo, Zhe CHEN, WANG Xiongfei, An estimator-based distributed voltage-predictive control strategy for AC islanded microgrids[J], IEEE Transactions on Power Electronics, 30, 7, pp. 3934-3951, (2015)
  • [3] HU Xuefeng, ZHANG Yubo, GAO Benbao, A transformerless integrated boost photovoltaic inverter without leakage currents[J], Proceedings of the CSEE, 39, 11, pp. 3344-3352, (2019)
  • [4] WU Weimin, Yuan LIU, HE Yuanbin, Damping methods for resonances caused by LCL-filter-based current-controlled grid-tied power inverters:an overview [J], IEEE Transactions on Industrial Electronics, 64, 9, pp. 7402-7413, (2017)
  • [5] YANG Jiaqiang, YANG Lei, ZENG Zheng, A current control method for LCL active power filters based on the reduced order generalized integrator[J], Proceedings of the CSEE, 37, 7, pp. 2057-2067, (2017)
  • [6] HUANG Yashen, WANG Haining, MA Zhibao, Review on researches of resonance suppression for grid-connected inverter system[J], Journal of Power Supply, 16, 4, pp. 143-156, (2018)
  • [7] AGORRETA J L,, BORREGA M, LOPEZ J, Modeling and control of N-paralleled grid-connected inverters with LCL filter coupled due to grid impedance in PV plants[J], IEEE Transactions on Power Electronics, 26, 3, pp. 770-785, (2011)
  • [8] Chen ZHENG, ZHOU Lin, XIE Bao, The harmonic resonance suppression strategy of large-scale photovoltaic plants based on phase margin compensation[J], Transactions of China Electrotechnical Society, 31, 19, pp. 85-96, (2016)
  • [9] WANG Fei, DUARTE J L,, HENDRIX M A M, Modeling and analysis of grid harmonic distortion impact of aggregated DG inverters[J], IEEE Transactions on Power Electronics, 26, 3, pp. 786-797, (2011)
  • [10] XU Dezhi, WANG Fei, MAO Hualong, Modeling and analysis of harmonic interaction between multiple grid-connected inverters and the utility grid[J], Proceedings of the CSEE, 33, 12, pp. 64-71, (2013)