Novel DC bus voltage control strategy for three-phase four-wire active power filter

被引:0
作者
Feng, Xia [1 ]
Zhong, Xiao-Jian [1 ]
Xu, Qun-Wei [1 ]
Chen, Guo-Zhu [1 ]
机构
[1] College of Electrical Engineering, Zhejiang University, Hangzhou
来源
Zhejiang Daxue Xuebao (Gongxue Ban)/Journal of Zhejiang University (Engineering Science) | 2014年 / 48卷 / 07期
关键词
Active power filter(APF); Balance-voltage loop; PI controller; Second-order low pass filter; Stable-voltage loop; Three-phase four-wire;
D O I
10.3785/j.issn.1008-973X.2014.07.024
中图分类号
学科分类号
摘要
Considering the characteristics of the DC bus voltage control of three-phase four-wire active power filter (APF), a stable-voltage loop and a balance-voltage loop with second-order low pass filter were designed according to the mathematic model of main circuit of system. The purpose of the two loops is to overcome the DC voltage fluctuation and unbalance between up-and-down capacitors during the APF system working. Compared with the traditional PI control method, the proposed strategy can achieve better control performance and control effect proved by theoretical analysis. Experimental results were conducted to validate the effectiveness of the proposed strategy.
引用
收藏
页码:1312 / 1317
页数:5
相关论文
共 7 条
  • [1] Guo X.-F., Wang D.-Z., Chen R.-Y., Et al., Active power filter DC bus voltage control based on fuzzy PI compound control , World Automation Congress (WAC), pp. 1-4, (2012)
  • [2] Dixon J., Contardo J., Moran L., DC link fuzzy control for an active power filter, sensing the line current only , Power Electronics Specialists Conference, pp. 1109-1114, (1997)
  • [3] Li Q.-L., Liu H.-J., Sun J.-J., Et al., Fuzzy-PI control used in APF , Electric Power Automation Equipment, 25, 10, pp. 17-21, (2005)
  • [4] Wang D., Wang X., Song K., Et al., An adaptive control method of shunt active power filter DC bus voltage , International Conference on Digital Manufacturing and Automation (ICDMA), pp. 172-176, (2011)
  • [5] Zeng Y.-Z., Zhang Z.-C., Zeng J.-L., Et al., Novel voltage control strategy to improve the dynamic performance of active power filter , Automation of Electric Power Systems, 13, pp. 43-46, (2006)
  • [6] Chen X., Hong L., Chen G.-Z., Design of DC-bus voltage controller for HAPF using low-pass filter , IECON 2011 - 37th Annual Conference on IEEE Industrial Electronics Society, pp. 1295-1299, (2011)
  • [7] Wang Z.-Q., Xie C., Zhang J., Et al., Dynamic DC-bus voltage control strategies for a three-phase high power shunt active power filter , Applied Power Electronics Conference and Exposition (APEC), pp. 1514-1520, (2010)