Experimental study on retrofitting of 500 kV transmission tower against ice load

被引:0
|
作者
Xie, Qiang [1 ]
Sun, Li [1 ]
Zhang, Yong [2 ]
机构
[1] College of Civil Engineering, Tongji University, Yangpu District, Shanghai 200092, China
[2] East China Grid Company Limited, Huangpu District, Shanghai 200002, China
关键词
Deformation - Electric power transmission - Ice - Towers - Buckling - Outages - Load limits - Loads (forces) - Retrofitting - Diaphragms;
D O I
暂无
中图分类号
学科分类号
摘要
In order to develop an effective retrofitting scheme for increasing the load-carrying capacity of transmission tower against ice load, two pairs of subassemblages for power transmission tower were established based on a typical 500 kV transmission tower which was severely damaged during the ice disaster. Each pair was designed with current code; while an additional diaphragm was added to its counterpart as a measure of retrofitting. The comparative tests on mechanical behavior, failure pattern and ice load-carrying capacity of the structures were conducted. The favorable effect of adding diaphragm in terms of improving structural performance of tower subassemblages was investigated. FEM software ANSYS was employed to analyze the behavior of the subassemblages by using shell elements. The study revealed that after adding diaphragm the out-of-plane deformation in the joints of cross-bracings was reduced significantly. Buckling mode of the main member was transited from torsional-flexural buckling to flexural buckling. And for one-panel and two-panel tower subassemblages, the ultimate strength was increased by 18.3% and 17.6% respectively. The diaphragm comprehensively improved the mechanical performance of transmission tower structures by decreasing the unfavorable influence of torsion of main member, and together with inhibiting the out-of-plane deformation of diagonal braces. Adding diaphragm is an effective and practical retrofitting method for enhancing the ice load-carrying capacity of transmission tower structures. © 2011 Chin. Soc. for Elec. Eng.
引用
收藏
页码:108 / 114
相关论文
共 50 条
  • [1] Experimental analysis on failure mechanism of 500 kV transmission tower under ice loading
    Xie, Qiang
    Sun, Li
    Gaodianya Jishu/High Voltage Engineering, 2010, 36 (12): : 3090 - 3096
  • [2] Failure mechanism and retrofitting strategy of transmission tower structures under ice load
    Xie, Qiang
    Sun, Li
    JOURNAL OF CONSTRUCTIONAL STEEL RESEARCH, 2012, 74 : 26 - 36
  • [3] Experimental study on lightning surge response of 500-kV transmission tower with overhead lines
    Motoyama, Hideki
    Kinoshita, Yasuhide
    Nonaka, Katsumasa
    IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (04) : 2488 - 2495
  • [4] Mathematical models study of wind load on superstructures of 500 kV single-circuit transmission tower
    Zhang, Qing-Hua
    Gu, Ming
    Huang, Peng
    Zhendong yu Chongji/Journal of Vibration and Shock, 2009, 28 (12): : 151 - 154
  • [5] Experimental study on failure modes and retrofitting method of latticed transmission tower
    Xie, Qiang
    Zhang, Jian
    ENGINEERING STRUCTURES, 2021, 226
  • [6] Experimental study on ice monitoring method for 10 kV transmission line with tangent tower in alpine landform
    Yang, Lin
    Chen, Zhiqiang
    Hao, Yanpeng
    Lin, Xinhao
    Yu, Lei
    Li, Yue
    Yuan, Zhiyong
    Li, Licheng
    HIGH VOLTAGE, 2024, 9 (01) : 182 - 194
  • [7] Experimental and Analytical Studies on Lightning Surge Response of 500-kV Transmission Tower
    Motoyama, Hideki
    Kinoshita, Yasuhide
    Nonaka, Katsumasa
    Baba, Yoshihiro
    IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (04) : 2232 - 2239
  • [8] Simulation and experimental analysis of corona loss of 1000 kV and 500 kV AC transmission lines on same tower
    Xie, Xiongjie
    Liu, Qin
    Huo, Feng
    Zhu, Lei
    Liu, Yunpeng
    Zhou, Guoyang
    Gaodianya Jishu/High Voltage Engineering, 2013, 39 (03): : 592 - 596
  • [9] Buckling Analysis of Transmission Tower Considering Ice Load
    Chen, Junqi
    Xian, Qingjun
    Zhang, Peng
    2018 5TH INTERNATIONAL CONFERENCE ON ADVANCED MATERIALS, MECHANICS AND STRUCTURAL ENGINEERING (AMMSE), 2019, 473
  • [10] System reliability of a transmission tower under ice load
    Xiong, Tiehua
    Hou, Jianguo
    An, Xuwen
    Li, Feng
    Tumu Gongcheng Xuebao/China Civil Engineering Journal, 2010, 43 (10): : 8 - 13