An Approach for Measuring the Zero Sequence Parameters of Mix-Voltage Quadruple-Circuit Transmission Lines on One Tower

被引:0
|
作者
Ni S. [1 ]
Hu Z. [1 ]
Yang A. [1 ]
Fu C. [1 ]
机构
[1] School of Electrical Engineering, Wuhan University, Wuhan
来源
Hu, Zhijian (zhijian_hu@163.com) | 2018年 / China Machine Press卷 / 33期
关键词
distributed parameter model; Mix-voltage quadruple-circuit transmission lines on one tower; synchronous measurement; zero sequence parameters;
D O I
10.19595/j.cnki.1000-6753.tces.170463
中图分类号
学科分类号
摘要
The electromagnetic coupling of mix-voltage quadruple-circuit transmission lines is complex which leads many zero sequence parameters needed to be measured. The existing methods can’t accurately measure these parameters. A method to accurately measure the zero sequence parameters of mix-voltage quadruple-circuit transmission lines was proposed. The distributed parameter model of the mix-voltage quadruple-circuit transmission lines was established. The transmission matrix which was related with these zero sequence parameters was obtained by solving transmission equations. The synchronous voltage and current data measured at the two ends of the four circuits and the transmission matrix were employed. And the calculation method of 18 zero sequence parameters was derived. Induced voltage interference was considered and an incremental method was put forward to eliminate it. PSCAD was employed to verify the proposed measurement method. The simulation results show that the proposed method overcomes the distribution effect of long distance transmission lines. The measurement model of the existing method was modified. The problem that the distributed parameter model of the existing method is not accurate enough was solved. The proposed method was hardly affected by the initial theoretical values and can apply to quadruple-circuit transmission lines with any voltage classes. The measurement procedure is simple and the proposed method can be used in the transmission lines which are completely or partly out of service. © 2018, Electrical Technology Press Co. Ltd. All right reserved.
引用
收藏
页码:2468 / 2478
页数:10
相关论文
共 26 条
  • [21] Liang R., Yang X., Xue X., Et al., Study of accurate single-phase grounding fault location based on distributed parameter theory using data of zero sequence components, Transactions of China Electrotechnical Society, 30, 12, pp. 472-479, (2015)
  • [22] Hu Z., Xiong M., Li Y., Et al., Measurement method of zero sequence parameters of EHV four-circuit transmission lines on the same tower, Proceedings of the CSEE, 35, 17, pp. 4548-4556, (2015)
  • [23] Deng J., Xiao Y., Hao Y., Measuring of distributed parameter and its application for dual-loop HVDC transmission lines on same tower, Electric Power Automation Equipment, 36, 3, pp. 154-158, (2016)
  • [24] Liu Q., Tai N., Fan C., Et al., Phase-mode transformation of asymmetry-parameter four-parallel lines on the same tower, Transactions of China Electrotechnical Society, 30, 18, pp. 171-180, (2015)
  • [25] Tripathy P., Srivastava S.C., Singh S.N., A modified TLS-ESPRIT-based method for low-frequency mode identification in power systems utilizing synchrophasor measurements, IEEE Transactions on Power Systems, 26, 2, pp. 719-727, (2011)
  • [26] Zhao Y., Chen X., Yin J., Et al., A new measurement method of the power frequency impedance parameters of double-circuit transmission lines on same tower, Transactions of China Electrotechnical Society, 20, 2, pp. 255-260, (2015)