Research and application of substation safety communication technology based on MMS alternative protocol

被引:0
作者
Luo H. [1 ]
Xu A. [2 ]
Lu C. [1 ]
Ruan L. [1 ]
Du Q. [3 ]
Wang S. [2 ]
机构
[1] Research Institute of State Grid Zhejiang Electric Power Co., Ltd., Hangzhou
[2] Beijing Sifang Jibao Engineering Technology Co., Ltd., Beijing
[3] State Grid Zhejiang Electric Power Co., Ltd., Hangzhou
来源
Dianli Zidonghua Shebei/Electric Power Automation Equipment | 2021年 / 41卷 / 12期
关键词
Encryption; Identity authentication; MMS alternative protocol; Safety communication; SM2; algorithm; Substation;
D O I
10.16081/j.epae.202107013
中图分类号
学科分类号
摘要
At present, most substations are built based on IEC61850 standard, and the in-station communication protocols mainly include MMS(Manufacturing Message Specification), GOOSE(Generic Objective-Orient Substation Event), SMV(Sampling Measurement Value), and so on, which gradually exposes some deficiencies and security risks in engineering application practice. Therefore, based on MMS alternative protocol, its function and safety protection technology are introduced emphatically. In terms of functionality, the MMS alternative protocol adds multiple services and optimizes the shortcomings of the existing MMS protocol. In terms of safety protection technology, the application layer of MMS alternative protocol realizes the two-way identity authentication based on SM2 algorithm and scheduling certificate, which can prevent illegal access and attack of unauthorized devices and eliminate the insecurity of device connection from the source of protocol. The transmission layer of MMS alternative protocol realizes the full link encryption and authentication based on SM2 algorithm and scheduling certificate, which ensures that the transmitted data message is anti-forgery, anti-repudiation and anti-theft, and protects the confidentiality and integrity of data message. The test results show that the MMS alternative protocol has certain reference significance in engineering application. © 2021, Electric Power Automation Equipment Press. All right reserved.
引用
收藏
页码:206 / 211
页数:5
相关论文
共 17 条
[1]  
LIU Kun, HUANG Minghui, LI Yiquan, Et al., Fault information model and online monitoring method for relay protection system in smart substation, Electric Power Automation Equipment, 38, 2, pp. 210-216, (2018)
[2]  
PENG Zhiqiang, ZHANG Qibing, SU Dawei, Et al., Remote ope-ration and maintenance technology of substation supervisory control system based on GPS, Electric Power Automation Equipment, 39, 4, pp. 210-216, (2019)
[3]  
16, 14
[4]  
ZHANG Yejia, Analysis of the environment of autonomy and controllability in our country, Electronics Quality, 7, pp. 58-61, (2019)
[5]  
ZHANG Jinhu, ZHANG Yue, SHEN Yan, Et al., An efficient and secure lightweight message authentication scheme for smart substation, Smart Power, 46, 11, pp. 53-58, (2018)
[6]  
FANG Fang, WANG Donghui, XUAN Xiaohua, Et al., Research on telecontrol communication of smart substation based on TLS connection, Electric Engineering, 8, pp. 75-77, (2019)
[7]  
26, (2019)
[8]  
REN Yanming, CAO Fengmei, TANG Xi, Et al., Advice on com-munication standards for smart grid, Automation of Electric Power Systems, 35, 3, pp. 1-4, (2011)
[9]  
ZHANG Ximing, LI Jin, QIU Rongfu, Et al., Research and application of national cryptographic series technology in smart substation, Southern Power System Technology, 14, 1, pp. 39-45, (2020)
[10]  
XU Ai, LIU Gang, XU Yanming, Security protection technology of smart substation based on SM9 identity-based cryptographic, Automation Panorama, 35, pp. 65-71, (2018)