Performance-based fire safety evacuation of an auditorium facility using a theoretical calculation method

被引:5
作者
Mahmoud A.S. [1 ]
Sanni-Anibire M.O. [1 ]
Hassanain M.A. [2 ]
机构
[1] Safety Technology Program, Dammam Community College, King Fahd University of Petroleum and Minerals, Dhahran
[2] Architectural Engineering Department, King Fahd University of Petroleum and Minerals, Dhahran
来源
Hassanain, Mohammad A. (mohhas@kfupm.edu.sa) | 1600年 / Emerald Group Holdings Ltd.卷 / 35期
关键词
Auditorium; Building code; Escape; Evacuation time; Fire safety;
D O I
10.1108/IJBPA-11-2016-0027
中图分类号
学科分类号
摘要
Purpose: The purpose of this paper is to present the findings of a theoretical calculation for the emergency evacuation of an auditorium facility managed by a university in Saudi Arabia. Design/methodology/approach: The authors reviewed the published literature to identify the sources of fire incidence, guidelines for means of escape in assembly occupancies and human behavior in fire emergencies. The theoretical method of the SFPE handbook to estimate the required evacuation time was subsequently applied to a case study of an auditorium facility managed by a university located in Saudi Arabia. Finally, the authors developed recommendations for the performance-based fire safety evacuation of the auditorium facility under review. Findings: The study showed that a total of 6 minutes 39 seconds is needed to evacuate the whole auditorium. However, reviewed literature for assembly occupancies requires between 4 minutes 30 seconds and 6 minutes 24 seconds for total evacuation. Though, the calculated evacuation time is close to generally acceptable limits. It was noted that overcrowding and bottlenecks may be formed in some of the exit routes. Originality/value: This paper will stimulate and increase research and industry concern for performance-based design of assembly-type facilities. This will be of significant value to designers, engineers, facilities managers, and owners in ensuring the safety of occupants in assembly-type facilities. © 2017, © Emerald Publishing Limited.
引用
收藏
页码:124 / 138
页数:14
相关论文
共 50 条
[1]  
Black B.D., Life safety, fire protection, and mobility-impaired persons, Journal of Fire Protection Engineering, 16, pp. 26-29, (2002)
[2]  
Bukowski R.W., Emergency egress from building part 1: history and current regulations for egress systems design, (2008)
[3]  
Butler L., School auditorium fire cancels fundraiser at saguaro high, (2007)
[4]  
Buxton P., Metric Handbook: Planning and Design Data, (2015)
[5]  
Chang-Xing R., Zhang X., Zhang W., Analysis on the emergency evacuation capabilities in fire accidents of assembly occupancies, Journal of Safety Science and Technology, 6, 2, pp. 39-43, (2010)
[6]  
Chen T., Pan L., Zhang G., Study of human behavior before evacuation, Pedestrian and Evacuation Dynamics 2012, pp. 521-532, (2014)
[7]  
Choi J., Kim M., Choi H., Evacuation efficiency evaluation model based on Euclidean distance with visual depth, (2007)
[8]  
Chu G., Wang J., Wang Q., Time-dependent fire risk assessment for occupant evacuation in public assembly buildings, Structural Safety, 38, pp. 22-31, (2012)
[9]  
Dinenno P.J., Drysdale D., Beyler C.L., Walton W.D., SFPE Handbook of Fire Protection Engineering, (2008)
[10]  