An evaluation of selective grounding fault protective relaying technique performance on the ungrounded DC traction power supply system

被引:1
作者
Korea Railroad Research Institute, Korea, Republic of [1 ]
不详 [2 ]
机构
来源
Trans. Korean Inst. Electr. Eng. | 2012年 / 12卷 / 1964-1969期
关键词
Dc traction system model; Field test; Rail potential limit device; Selective grounding fault protective relay; Ungrounded dc traction;
D O I
10.5370/KIEE.2012.61.12.1964
中图分类号
学科分类号
摘要
This paper presents to verify the selective grounding fault protective relaying technique for the ungrounded DC traction power supply system. This system selectively blocks fault section when grounding fault occurred. In order to perform this verification, field test facilities have been installed on Oesam substation and Worldcup-Stadium substation, and field test process has been suggested. Also, selective grounding fault protective relaying components and rail voltage reduction device have been tested with the various trial examinations. In order to compare and evaluate performance of the selective grounding fault protective relaying function, field test system was modeled and the system fault simulation results were compared and evaluated with the field test result. Performance of selective grounding fault protective relaying function was evaluated with the above-mentioned process, and the fact that the system recognizes fault section irrespective of insulation between rail and ground and fault resistance from grounding fault.
引用
收藏
页码:1964 / 1969
页数:5
相关论文
共 6 条
  • [1] Kim S.-G., Urban Transit Technology Materials(7) Electricity, (2005)
  • [2] Min M.-H., An analysis on rise of rail potential and a study on control method for it in DC feeding system, The Transactions of the Korean Institute of Electrical Engineers, 60, 3, pp. 680-685, (2011)
  • [3] Investigation on Protection and Coordination of Protection System in DC Electric Railway, (1994)
  • [4] Kang S.-H., Integrated protection method for DC railway systems, The Transactions of the Korean Institute of Electrical Engineers, 60, 2, pp. 285-292, (2011)
  • [5] Choi C.-Y., Selective Ground Fault Protection Algorithm for DC Railway Systems, 5, pp. 55-57, (2009)
  • [6] An T.-P., Development of a simulator and algorithm test for selective-Breaking integrated protective relay for ungrounded DC traction power supply system, The Transactions of the Korean Institute of Electrical Engineers, 61, 6, (2012)