Impact of Grounding Conductor Corrosion on Grounding Resistance of Grounding Mesh and Improvement Method

被引:0
|
作者
Zhou L. [1 ]
He Z. [1 ]
Chen Y. [1 ]
Liu Y. [1 ]
He J. [1 ]
Qiu Q. [1 ]
机构
[1] School of Electric Engineering, Southwest Jiaotong University, Chengdu
来源
关键词
Corrosion; Grounding conductor; Grounding mesh; Grounding resistance;
D O I
10.3969/j.issn.1001-8360.2018.02.006
中图分类号
学科分类号
摘要
The grounding mesh of traction substations plays a key role in the safe and stable operation of the traction power supply system. With the increase of the operation time of the grounding mesh, the characteristic parameters in excess of the standard caused by grounding conductor corrosion, are harmful to the safe and stable operation of the traction power supply system. In this paper, the CDEGS professional grounding simulation software was used to carry out the simulation calculation, to analyze the influence of grounding conductor corrosion on the grounding resistance of the grounding mesh, when the soil resistivity, grounding mesh area and grounding mesh equalizing conductor arrangement method are different. Results show that, with the decrease of soil resistivity, the degree of grounding conductor corrosion increases, resulting in greater impact on the grounding resistance. Under the same corrosion conditions, the wider the grounding mesh area, the greater the grounding resistance of the grounding mesh.Under the same grounding mesh area and steel consumption, through a reasonable choice of grounding mesh equalizing conductor arrangement method, the influence of corrosion on the grounding resistance of grounding mesh can be reduced to achieve economic and technological optimization. © 2018, Department of Journal of the China Railway Society. All right reserved.
引用
收藏
页码:39 / 44
页数:5
相关论文
共 21 条
  • [1] Li Q., On Some Technical Key Problems in the Development of Traction Power Supply System for High-speed Railway in China, Journal of the China Railway Society, 32, 4, pp. 119-124, (2010)
  • [2] 80-2000 Guide for Safety in AC Substation Grounding, (2000)
  • [3] Gonos I.F., Stathopulos I.A., Estimation of Multilayer Soil Parameters Using Genetic Algorithms, IEEE Transactions on Power Delivery, 20, 1, pp. 100-106, (2005)
  • [4] Tan B., Yang J., Wen X., Et al., Safety Design Principle of Grounding System in Large Hydropower Station in the Area of High Soil Resistivity, High Voltage Engineering, 37, 10, pp. 2485-2490, (2011)
  • [5] Takahashi T., Kawase T., Analysis of Apparent Resistivity in a Multilayer Earth Structure, IEEE Transactions on Power Delivery, 5, 2, pp. 604-612, (1990)
  • [6] Lu Z., Chang S., Li Y., Et al., Difference between the Grounding Impedance and Grounding Resistance of Large Substation Grounding Grids, High Voltage Engineering, 31, 1, pp. 1-3, (2005)
  • [7] He J., Zhang B., Zeng R., Et al., Grounding System Design of 1 000 kA Ultra-high Voltage Substation, Proceedings of the CSEE, 29, 7, pp. 7-12, (2009)
  • [8] Sverak J.G., Optimized Grounding Grid Design Using Variable Spacing Techniques, IEEE Transactions on PAS, 95, 1, pp. 362-374, (1976)
  • [9] Dawalibi F., Mukhedkar D., Optimized Design of Substation Grounding in Two Layer Structure, Part I: Analytical Study, IEEE Transactions on PAS, 94, 2, pp. 252-261, (1975)
  • [10] Chang Y., Wang M., Xu C., Et al., Equilibrium Optimization of Potential Differences Within Grounding Mesh, Power System Technology, 32, 22, pp. 98-102, (2008)