Parameter identification based on vector fitting method for extended debye model of oil-paper insulation system

被引:0
作者
机构
[1] State Key Laboratory of Electrical Insulation and Power Equipment, Xi'an Jiaotong University
[2] Henan Electric Power Research Institute
[3] Jiaozuo Power Supply Company
来源
Tang, M. (tmj_1030@163.com) | 1600年 / Science Press卷 / 40期
关键词
Extended Debye model; Fast Fourier transform; Frequency domain spectrum; Oil-paper insulation; Parameter identification; Polarization and depolarization current; Vector fitting method;
D O I
10.13336/j.1003-6520.hve.2014.02.030
中图分类号
学科分类号
摘要
In order to obtain more specific information of insulation states of oil-paper insulation system from time-domain data, we proposed a novel method for parameter identification of extended Debye model for oil-paper insulation system. In the method, the depolarization current spectrum of polarization and depolarization current (PDC) in experiments was obtained by the fast Fourier transform (FFT). Then combining the vector fitting method (VFM) and nonlinear fitting algorithm (FNA), we derived the distribution of the poles and residues of the obtained spectrum, and calculated the branch parameters of extended Debye models. The PDC and frequency domain spectrum (FDS) measurements were performed on some oil-impregnated pressboard samples, which were in various aging states and under different temperatures. The corresponding extended Debye models to the samples were obtained from the PDC measurement, based on which curves of tanδ varying with frequency were figured out and then compared with those from FDS measurements. The tanδ obtained from PDC agrees well with that from FDS under low frequencies, which verifies the proposed method. With further analysis, it is suggested that, for oil-paper insulation system, FDS measurement should be conducted in high frequency range but replaced by PDC measurement in low frequency range, for saving time, i. e. the combination of FDS and PDC methods could help to improve the efficiency of measurement of on-site oil-paper equipment.
引用
收藏
页码:548 / 556
页数:8
相关论文
共 50 条
  • [31] Investigating the Impacts of Temperature on the Dielectric Response of Oil-paper Insulation System
    Peng, Hua-dong
    Dong, Ming
    Ren, Ming
    Wei, Jian-lin
    Miao, Jin
    Wu, Xue-zhou
    PROCEEDINGS OF 2011 INTERNATIONAL CONFERENCE ON ELECTRICAL INSULATING MATERIALS (ISEIM), 2011, : 233 - 236
  • [32] Residual Life Assessment Method of Transformer Oil-Paper Insulation Aging Based on Wiener Modle
    Zhang M.
    Liu J.
    Chen X.
    Liao L.
    Chen Q.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2018, 33 (21): : 5098 - 5108
  • [33] Research on oil-paper insulation based on the integral of frequency domain spectrum
    Zhang T.
    Liu Y.-Q.
    Yang W.-Y.
    Zhang C.
    Ren Q.-L.
    Xiao S.
    Dianji yu Kongzhi Xuebao/Electric Machines and Control, 2019, 23 (07): : 72 - 78
  • [34] Research on Life Prediction of Oil-Paper Insulation Based on Dielectric Response
    Liu, Ji
    Lv, Jialu
    Zhang, Mingze
    Jia, Haifeng
    Zhuang, Weitao
    Chen, Xin
    ELECTRIC POWER COMPONENTS AND SYSTEMS, 2020, 48 (03) : 281 - 290
  • [35] Characteristic Parameters Extraction of Oil-paper Insulation Aging Based on Davidson-Cole model
    Zhang Weili
    Liu Ji
    Zhang Mingze
    Liao Lilin
    Xu Helin
    2018 12TH INTERNATIONAL CONFERENCE ON THE PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS (ICPADM 2018), 2018, : 443 - 446
  • [36] Aging Condition Assessment of Transformer Oil-paper Insulation Model based on Partial Discharge Analysis
    Liao, Rui-jin
    Yang, Li-jun
    Li, Jian
    Grzybowski, Stanislaw
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2011, 18 (01) : 303 - 311
  • [37] State Assessment of Oil-paper Insulation Based on Fuzzy Rough Sets
    He, Dehua
    Wang, Ruliang
    2019 15TH INTERNATIONAL CONFERENCE ON COMPUTATIONAL INTELLIGENCE AND SECURITY (CIS 2019), 2019, : 438 - 441
  • [38] Influence of Insulation Model Parameters on Transfer Function Zero Evaluated for Diagnosis of Oil-paper Insulation
    Banerjee, C. M.
    Saurabh
    Baral, A.
    Chakravorti, S.
    2017 3RD INTERNATIONAL CONFERENCE ON CONDITION ASSESSMENT TECHNIQUES IN ELECTRICAL SYSTEMS (CATCON), 2017, : 375 - 379
  • [39] Equivalent Nonlinear Circuit Model with Interface Charge and Polarity Effect for Oil-Paper Composite Insulation
    Huang M.
    Li Y.
    Wu Y.
    Chen L.
    Qi B.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2024, 39 (11): : 3422 - 3432
  • [40] An Improved Mathematical Model for Estimating Polarization Parameters of Transformer Oil-Paper Insulation
    Tao Zhang
    Antonio Tome Mandala
    Qian Zuo
    Ning Zhang
    Shijie Jiang
    Journal of Electrical Engineering & Technology, 2022, 17 : 2517 - 2525