Transient Power Based Single-end Protection for HVDC Transmission Line

被引:0
|
作者
Hou J. [1 ]
Song G. [1 ]
Chang Z. [1 ]
Zhang C. [1 ]
Wu L. [1 ]
Wang T. [1 ]
机构
[1] School of Electrical Engineering, Xi'an Jiaotong University, Xi'an
来源
Dianli Xitong Zidonghua/Automation of Electric Power Systems | 2019年 / 43卷 / 21期
基金
中国国家自然科学基金;
关键词
Boundary protection; High-voltage direct current (HVDC); Line protection; Single-end protection; Transient power;
D O I
10.7500/AEPS20181126010
中图分类号
学科分类号
摘要
Aiming at the problem of low reliability of traditional single-ended protection for high-voltage direct current (HVDC) lines, by considering the influence of DC boundary, line parameter frequency variation and other factors, this paper studies the transient power fault characteristics of HVDC lines, and puts forward a scheme of single-end protection based on transient power. According to the difference in the frequency band of fault transient power in and out of the positive direction, using the ratio of transient energy between high and low frequency bands, a boundary protection element is built. Considering the limitation of using frequency attenuation characteristics of transient power to distinguish positive and negative direction faults, a directional auxiliary criterion is constructed by using transient power polarity. Combined with the actuating element and the fault pole element, the single-end protection scheme based on transient power is constructed. The simulation results show that the scheme can distinguish the internal and external faults of DC line area rapidly and effectively, with certain resistance to transition resistance and anti-interference ability, and have high reliability. © 2019 Automation of Electric Power Systems Press.
引用
收藏
页码:203 / 212
页数:9
相关论文
共 25 条
  • [1] Zhou J., Zhao C., Li C., Et al., Pilot protection method for DC lines based on included angle cosine of fault current component, Automation of Electric Power Systems, 42, 14, pp. 165-171, (2018)
  • [2] Zheng C., Mo P., Wen J., Et al., Criterion and scheme for high-voltage capacitor earth fault protection of DC filter, Automation of Electric Power Systems, 42, 1, pp. 132-137, (2018)
  • [3] Zhou J., Zhao C., Li C., Et al., Boundary protection scheme for multi-terminal flexible DC grid based on voltage of DC reactor, Automation of Electric Power Systems, 41, 19, pp. 89-94, (2017)
  • [4] Zheng J., Wen M., Qin Y., Et al., A novel differential protection scheme with fault line selection capability for HVDC transmission line, Proceedings of the CSEE, 38, 15, pp. 4350-4358, (2018)
  • [5] Chen G., Li M., Xu T., System protection and its key technologies of UHV AC and DC power grid, Automation of Electric Power Systems, 42, 22, pp. 2-10, (2018)
  • [6] Yang Y., Tai N., Fan C., Et al., A pilot protection scheme for HVDC transmission lines based on specific-frequency, Proceedings of the CSEE, 37, 15, pp. 4304-4314, (2017)
  • [7] Liu Q., Song G., A novel pilot protection for HVDC transmission lines using mean current error control, Proceedings of the CSEE, 36, 8, pp. 2159-2167, (2016)
  • [8] Gao S., Suonan J., Song G., Et al., A novel whole-line quick-action protection principle for HVDC transmission lines using one-end currents, Proceedings of the CSEE, 32, 7, pp. 107-113, (2012)
  • [9] Zhang B., Kong F., Zhang S., Et al., Technical development of non-unit protection devices based on transient signals for HVDC transmission lines, Proceedings of the CSEE, 33, 4, pp. 179-185, (2013)
  • [10] Zhang B., Zhang S., You M., Et al., Research on transient-based protection for HVDC lines, Power System Protection and Control, 38, 15, pp. 18-23, (2010)