Water Tree Detection in Underground Cables Using Time Domain Reflectometry

被引:22
作者
Burkes, Klaehn W. [1 ]
Makram, Elham B. [2 ]
Hadidi, Ramtin [2 ,3 ]
机构
[1] Savannah River National Laboratory, Aiken, 29808-0001, SC
[2] Holcombe Department of Electrical and Computer Engineering, Clemson University, Clemson, 29634, SC
[3] Clemson University Restoration Institute, North Charleston, 29405, SC
来源
IEEE Power and Energy Technology Systems Journal | 2015年 / 2卷
关键词
Time domain reflectometry (TDR); underground residential distribution (URD); water tree;
D O I
10.1109/JPETS.2015.2420791
中图分类号
学科分类号
摘要
This paper proposes to use time domain reflectometry (TDR) to detect water trees in underground residential distribution (URD) cables. Water trees are very dangerous to underground cables. They can grow for years without any change on the performance of the cable, and then can cause the cable to fault unexpectedly. Therefore, a method to detect water trees in URD cables is proposed in this paper. The method implements an optimal pulse generator placement algorithm on a distribution feeder for performing TDR. It can determine the exact location of a water tree in a cable, and it does not rely on the length of the cable or the type of cable used. The method can also detect multiple water trees on the same cable, and can be installed on existing systems, since it does not require data of the healthy system. It is a periodic monitoring system where pulses are sent throughout the year. The proposed method has been verified using multiple case studies on a real distribution feeder. Using TDR, optimal pulse generator placement, and subtraction of cables' measured signal in time domain with similar measured signals a critical distribution feeder's health has been monitored successfully. © 2015 IEEE.
引用
收藏
页码:53 / 62
页数:9
相关论文
共 22 条
[1]  
Densley J., Ageing mechanisms and diagnostics for power cables-An overview, IEEE Elect. Insul. Mag., 17, 1, pp. 14-22, (2001)
[2]  
Thue W.A., Treeing, Electric Power Cable Engineering, pp. 367-384, (2012)
[3]  
Mejia J.C.H., Characterization of Real Power Cable Defects by Diag-nostic Measurements, (2008)
[4]  
Acedo M., Radu I., Frutos F., Filippini J.C., Notingher P., Water treeing in underground power cables: Modelling of the trees and calcu-lation of the electric field perturbation, J. Electrostatics, 53, 4, pp. 267-294, (2001)
[5]  
Toyoda T., Mukai S., Ohki Y., Li Y., Maeno T., Estimation of conductivity and permittivity of water trees in PE from space charge dis-tribution measurements, IEEE Trans. Dielectr. Electr. Insul., 8, 1, pp. 111-116, (2001)
[6]  
Dubickas V., On-line Time Domain Reflectometry Diagnostics of Medium Voltage XLPE Power Cables, (2006)
[7]  
Gonzalez A.G., Paprotny I., White R.M., Wright P.K., Novel online RF technique for detection of water trees in underground pow-ered distribution cables, Proc. Elect. Insul. Conf. (EIC), pp. 345-348, (2011)
[8]  
AC/DC Module, (2013)
[9]  
Burkes K., Makram E., Hadidi R., Modeling the effect of a water tree inside tape shield and concentric neutral cables, Proc. COMSOL Conf., pp. 1-9, (2014)
[10]  
Wang Z., Evans J.W., Wright P.K., Thermodynamics of water treeing, IEEE Trans. Dielectr. Electr. Insul., 18, 3, pp. 840-846, (2011)