Experimental study of heat and mass transfer of saltwater cooling tower

被引:0
作者
Wang, Chao [1 ]
Dong, Fei-Ying [1 ]
Fan, Li-Wu [1 ]
Yu, Zi-Tao [1 ]
Hu, Ya-Cai [1 ]
机构
[1] Institute of Thermal Science and Power Systems, Zhejiang University
来源
Hu, Y.-C. (huyacai@zju.edu.cn) | 1600年 / Zhejiang University卷 / 48期
关键词
Characteristics of heat and mass transfer; Cooling tower; Saltwater;
D O I
10.3785/j.issn.1008-973X.2014.04.016
中图分类号
学科分类号
摘要
Experiments were performed on a mechanical-draft counter-flow cooling tower to analyze the heat and mass transfer of saltwater cooling towers at high concentrations. By maintaining the inlet saltwater temperature at 28~50°C, the effects of mass fraction of the saltwater (6%, 12%, 16%, 25%, and 34% aqueous CaCl2 solutions) and Reynolds number Re (ranging between 2000~16000) on the non-dimensional heat and mass transfer coefficients, NuV and ShV were respectively analyzed. Results show that self-scaling phenomenon is occurred in packing layer of saltwater cooling tower, and the NuVPr-1/3 and ShVSc-1/3 are nearly independent of Re. The heat and mass transfer performance of the cooling towers deteriorates with increasing the concentration of the saltwater. When the mass fraction is increased from 6% to 34%, NuVPr-1/3 and ShVSc-1/3 are decreased by 51.5% and 45.8%, respectively. Correlations of NuVPr-1/3 and ShVSc-1/3 to the variation of concentration were proposed based on linear curve fitting.
引用
收藏
页码:666 / 670+710
相关论文
共 21 条
  • [1] Lemouari M., Boumaza M., Mujtaba I.M., Thermal performances investigation of a wet cooling tower, Applied Thermal Engineering, 27, 5-6, pp. 902-909, (2007)
  • [2] Bedekar S.V., Nithiarasu P., Seetharamu K.N., Experimental investigation of the performance of a counter flow packed bed mechanical cooling tower, Energy, 23, 11, pp. 943-947, (1998)
  • [3] Nester D.M., Salt water cooling tower, Chemical Engineering Progress, 67, 7, pp. 49-51, (1971)
  • [4] Liu J.-P., Yan J.-J., Xing Q.-A., Et al., A method and system for water conservation of cooling towers
  • [5] Hu Y.-C., Ruan G.-Z., Wang H.-M., Et al., Natural-draft saltwater cooling towers
  • [6] Narayan G.P., Mistry K.H., Sharqawy M.H., Et al., Energy effectiveness of simultaneous heat and mass exchange devices, Frontiers in Heat and Mass Transfer, 1, 2, pp. 1-13, (2010)
  • [7] Sharqawy M.H., Lienhaed V.J.H., Zubair S.M., On thermal performance of seawater cooling towers, Journal of Engineering for Gas Turbines and Power, 133, 4, (2011)
  • [8] (2007)
  • [9] Onda K., Takeuchi H., Okumoto Y., Mass transfer coefficients between gas and liquid phases in packed columns, Journal of Chemical Engineering of Japan, 1, 1, pp. 56-62, (1968)
  • [10] Xia Q.-M., Experimental study of water-saving cooling tower and double-effect plastic LiBr absorption chiller, (2011)