Research on Characteristics of Partial Electric Arc on Contaminated Insulating Surface Attached With Floating Potential Metal

被引:0
|
作者
Wang Y. [1 ]
Mu L. [1 ]
Wang W. [2 ]
Wang W. [2 ]
Pei H. [1 ]
Wen X. [1 ]
Lan L. [1 ]
机构
[1] School of Electrical Engineering and Automation, Wuhan University, Wuhan, 430072, Hubei
[2] Electric Power Research Institute, State Grid Hubei Electric Power Corporation, Wuhan, 430077, Hubei
基金
中国国家自然科学基金;
关键词
Attached metal floating potential; Composite insulating material tower; Distorted electric field; Drying belt; Leakage current;
D O I
10.13334/j.0258-8013.pcsee.182335
中图分类号
学科分类号
摘要
In order to obtain the mechanism of partial discharge on contaminated insulation surface adhered with metal conductor, artificial contamination test of small size composite insulating material specimens attached with metal conductors was carried out. Combining with simulation analysis, the difference in the discharge phenomena caused by the relative size between width of contamination layer and adhered metal was studied in depth, which can provide a theoretical basis for proposing practical measures to suppress partial arcs. Test and simulation results show that dry band is the most essential factor affecting partial arc discharge. The location of the dry band and the location of the partial arc are determined by the suspended potential conductors. The relative size of fouling layer and attached conductor has obvious influence on partial discharge. When the width of the fouling layer is much larger than the size of the attached metal, the dry band can't penetrate the fouling layer. The maximum electric field strength of the dry band can't reach the initial electric field strength of the discharge, and there will always be no obvious partial arc near the metal. When the width of the fouling layer is about the same as the size of the attached metal, the dry band will penetrate the fouling layer and bear most of the voltage, so that the electric field strength exceeds the initial discharge field strength, and there will be obvious partial arc near the metal. © 2019 Chin. Soc. for Elec. Eng.
引用
收藏
页码:3253 / 3261
页数:8
相关论文
共 26 条
  • [1] Yang J., Li M., Yang F., Et al., New advances in the study of transmission tower structure of China, Power System Technology, 32, 22, pp. 77-83, (2008)
  • [2] Chen X., Liu Z., Xiao Q., Transmission Tower and Foundation Design, (2013)
  • [3] An L., Zhao D., Mo Z., Et al., Recent progress of fibre-reinforced polymer composite materials transmission poles and towers, Smart Grid, 2, 5, pp. 38-45, (2014)
  • [4] Miller M.F., Hosford G.S., Boozer J.F., Fiberglass distribution poles a case study, IEEE Transactions on Power Delivery, 10, 1, pp. 497-503, (1995)
  • [5] Dutt V., Lacoursiere B., Composite utility poles: advances in design, materials & manufacturing, 2005/2006 IEEE PES Transmission and Distribution Conference and Exhibition, (2006)
  • [6] Cao N., The applied research on composite material towers of 110kV transmission line, (2012)
  • [7] Hu Y., Liu T., Liu K., Et al., Experimental research on performance of composite materials pole of 110kV transmission line, High Voltage Engineering, 37, 4, pp. 801-807, (2011)
  • [8] Ren Z., Liu Q., Mo Z., Joint design and optimization of FRB tower, Electric Power Construction, 32, 4, pp. 87-91, (2011)
  • [9] Liu Z., Study on external insulation characteristics and configuration of composite insulating material tower, (2016)
  • [10] Zheng N., Study on contaminant discharge test and its restraining method on composite tower, (2014)