Study on Corona Characteristics and Type Selection of UHV Substation Conductor in 4000 m High Altitude Area

被引:0
|
作者
Liu P. [1 ]
Zhang J. [1 ]
Xie L. [2 ]
Li Y. [2 ]
Liu C. [1 ]
Peng Z. [1 ]
机构
[1] State Key laboratory of Electrical Insulation and Power Equipment, Xi’an Jiaotong University, Xi’an
[2] State Key Laboratory of Power Grid Environmental Protection, China Electric Power Research Institute Co., Ltd., Wuhan
来源
Gaodianya Jishu/High Voltage Engineering | 2023年 / 49卷 / 07期
关键词
4000 m high altitude; conductor selection; corona; substation; UHV;
D O I
10.13336/j.1003-6520.hve.20230322
中图分类号
学科分类号
摘要
The conductor connection modes in 1000 kV substation are various, and its surface electric field distribution is extremely uneven due to proximity effect. Corona discharge is easy to occur on the conductor surface, especially in high altitude areas, thus the corona voltage of the conductor will be reduced. In order to prevent the corona on the conductor surface and optimize the electromagnetic environment of the substation, a reasonable conductor type must be selected. We propose a method of substation conductor selection based on numerical calculation and finite element simulation and supplemented by corona simulation test. The control value of conductor surface field strength is obtained, and the Em/Ec, audible noise L50, and electric field distribution of conductor are calculated when different selection schemes are adopted. Besides, the conductor selection scheme of UHV substation at 4000 m altitude is given and verified by the corona tests. The results show that the recommended control value of conductor surface electric field strength is 1.84 kV/mm. Meanwhile, if the UHV substation at an altitude of 4000 m still uses four-bundle conductors, Em/Ec and L50 will increase by 50.0% and 23.7%, respectively. When the selection scheme recommended in this paper is adopted, Em/Ec and L50 are 0.79 and 60.29 dB, respectively, the maximum field strength on the conductor surface is 1.67 kV/mm, and the corona extinction voltage of the conductor at high altitude is 770 kV, which meets the requirements of corona protection of the conductor at 4000 m high altitude UHV substation. The research methods and results in this paper can provide a basis for the subsequent selection of UHV substation conductors in high-altitude areas and the construction of green and environmental protection power grid projects in China. © 2023 Science Press. All rights reserved.
引用
收藏
页码:2919 / 2928
页数:9
相关论文
共 33 条
  • [1] HAN Xiaoqing, LI Tingjun, ZHANG Dongxia, Et al., New issues and key technologies of new power system planning under double carbon goals, High Voltage Engineering, 47, 9, pp. 3036-3046, (2021)
  • [2] LI Qingmin, YU Wanshui, ZHAO Jiyao, Key technologies for the safe operation of wind and solar power generation equipment in support of the “peak CO2 emissions and carbon neutrality” policy, High Voltage Engineering, 47, 9, pp. 3047-3060, (2021)
  • [3] SHENG Gehao, QIAN Yong, LUO Lingen, Et al., Key technologies and application prospects for operation and maintenance of power equipment in new type power system, High Voltage Engineering, 47, 9, pp. 3072-3084, (2021)
  • [4] ZHAO Jingbo, HUANG Qiang, ZHAO Xiang, Et al., Analysis of restrictive factors of new energy consumption based on fuzzy dynamic evaluation, High Voltage Engineering, 48, 4, pp. 1286-1295, (2022)
  • [5] ZHOU Yuanxiang, CHEN Jianning, ZHANG Ling, Et al., Opportunity for developing ultra high voltage transmission technology under the emission peak, carbon neutrality and new infrastructure, High Voltage Engineering, 47, 7, pp. 2396-2408, (2021)
  • [6] YAO Liming, YIN Xiang, MENG Zhiyi, The problem of “abandoning water and electricity” in summer in the southwest region prevails, multiple measures are suggested to promote hydropower energy consumption during high water season, China Development, 22, 3, pp. 93-94, (2022)
  • [7] ZHAO Heng, CAO Kaijiang, ZHANG Tong, Exploration of Sichuan’s energy transformation path under the “double carbon” goal, China Power Enterprise Management, 16, pp. 66-68, (2022)
  • [8] REN Dawei, XIAO Jinyu, HOU Jinming, Et al., Construction and evolution of China’s new power system under dual carbon goal, Power System Technology, 46, 10, pp. 3831-3839, (2022)
  • [9] ZENG Qingyu, Study on electric characteristic and corona performance of UHV AC transmission line, Power System Technology, 31, 19, pp. 1-8, (2007)
  • [10] HUANG Zixuan, XI Liming, FAN Mengxu, Et al., Influence of corona discharge on power frequency electric field underneath UHV AC transmission lines, High Voltage Apparatus, 50, 2, pp. 6-11, (2014)