Single-ended Fault Location of Hybrid MMC-HVDC System Based on Active Detection

被引:0
作者
Song G. [1 ,2 ]
Hou J. [1 ,2 ]
Guo B. [1 ,2 ]
机构
[1] Shaanxi Key Laboratory of Smart Grid, Xi'an Jiaotong University, Xi'an
[2] School of Electrical Engineering, Xi'an Jiaotong University, Xi'an
来源
Dianwang Jishu/Power System Technology | 2021年 / 45卷 / 02期
基金
中国国家自然科学基金;
关键词
Active detection; Fault location; Hybrid MMC; Single ended;
D O I
10.13335/j.1000-3673.pst.2020.0200a
中图分类号
学科分类号
摘要
In order to further improve the performance of traditional fault location methods and ensure the reliability of DC line fault recovery, an active detection signal injection strategy is proposed based on the high controllability of hybrid MMC converter considering the influence of fault impedance, frequency-dependent parameters effect, numerical differential error and distributed capacity of transmission line. Based on the fault current limiting strategy and the idea of parameter identification, the compensation strategy of distributed parameter model is introduced to construct the parameter identification fault location equation with fault distance and transition resistance parameters to realize fault location. The simulation results show that the proposed fault location schemes can accurately identify the fault area, and are applicable for long DC lines and less affected by fault impedance and sampling rate. © 2021, Power System Technology Press. All right reserved.
引用
收藏
页码:730 / 740
页数:10
相关论文
共 25 条
[1]  
XueShimin, LianJie, Qi Jinlong, Et al., Fault transient characteristic and adaptive reclosing technique of MMC-HVDC network, Power System Technology, 42, 12, pp. 4015-4021, (2018)
[2]  
Lin W, Jovcic D, Nguefeu S, Et al., Full-bridge MMC converter optimal design to HVDC operational requirements, IEEE Transactions on Power Delivery, 31, 3, pp. 1342-1350, (2015)
[3]  
JiaKe, Li Meng, Bi Tianshu, Et al., Energy distribution based differential protection for VSC-DC distribution lines, Power System Technology, 41, 9, pp. 3058-3065, (2017)
[4]  
He Jinghan, Luo Yiping, Luo Guomin, Et al., A single-ended protection algorithm based on wavelet multi-resolution analysis and support vector machine for flexible DC systems, Power System Technology, 42, 12, pp. 4022-4030, (2018)
[5]  
Luo Yongjie, Li Yaohua, Li Zixin, Et al., DC short-circuit fault ride-through control strategy of full-bridge MMC-HVDC systems, Proceedings of the CSEE, 36, 7, pp. 1933-1943, (2016)
[6]  
Li Shaohua, Wang Xiuli, Li Tai, Et al., Optimal design for hybrid MMC and its DC fault ride-through strategy, Proceedings of the CSEE, 36, 7, pp. 1849-1858, (2016)
[7]  
Zhou Meng, Xiang Wang, Lin Weixing, Et al., Active current limiting control to handle DC line fault of overhead DC grid, Power System Technology, 42, 7, pp. 2062-2072, (2018)
[8]  
Zhang Junjie, Xiang Wang, Lin Weixing, Et al., DC fault protection of VSC-HVDC grid based on hybrid MMC and DC switch, ElectricPower Construction, 38, 8, pp. 52-58, (2017)
[9]  
Wang Shuai, Bi Tianshu, JiaKe, Single terminal fault location for MMC-HVDC transmission line using active pulse, Transactions of China Electrotechnical Society, 32, 1, pp. 12-19, (2017)
[10]  
Song Guobing, Wang Ting, Zhang Chenhao, Et al., Adaptive auto-reclosing of DC line based on characteristic signal injection with FB-MMC, Power System Technology, 43, 1, pp. 149-156, (2019)