A Robust Control Strategy for Eliminating the Structure Disturbance of Islanding Microgrid

被引:0
作者
Sun X. [1 ]
Ma H. [1 ]
Jia L. [1 ,2 ]
Li X. [1 ]
机构
[1] Key Lab of Power Electronics for Energy Conservation & Motor Drive of Hebei Province, Yanshan University, Qinhuangdao
[2] Key Lab of Electromagnetic Transformation and Detection of Henan Province, Luoyang Normal University, Luoyang
来源
Diangong Jishu Xuebao/Transactions of China Electrotechnical Society | 2020年 / 35卷 / 11期
关键词
Master-slave control; Mixed sensitivity; Robust control; Smart grid;
D O I
10.19595/j.cnki.1000-6753.tces.181500
中图分类号
学科分类号
摘要
The distributed generation devices are operated in parallel by solid state transformer (SST), after utilizeing the communication system, an intelligent microgrid can be formed, the master-slave control can be adopted by utilizeing the advantage of communication when the smart grid is running in islanded condition. During the operation of the system, if the slave is cut off because of the fault or reconnected after repaired, the structure of the system will be changed, which will affect the stability of the system. For dealing with this problem, the uncertainty of the master's model is analyzed in this paper, and then the robust controller is designed based on the mixed sensitivity for master-slave control of microgrid. The master uses the designed robust controller to supprot voltage for the entire system. Through the designed robust controller, the robustness of the system voltage to the disturbance caused by the change of the number of slaves is enhanced, so that the system voltage amplitude and frequency can be stabilized when the number of slaves or load changes. Finally, the simulation and experimental verification of the Matlab/Simulink simulation platform and the RTDS controller hardware in the loop (CHIL) platformare carried out. The results show the effectiveness of the proposed controller. © 2020, Electrical Technology Press Co. Ltd. All right reserved.
引用
收藏
页码:2427 / 2438
页数:11
相关论文
共 27 条
[1]  
Cong Wei, Sheng Yaru, Xian Guofu, Et al., Distributed power service restoration method based on smart terminal unit, Automation of Electric Power Systems, 42, 15, pp. 77-85, (2018)
[2]  
Xiao Xiangning, Wang Peng, Chen Meng, Secondary voltage control in an islanded microgrid based on distributed multi-agent system, Transactions of China Electrotechnical Society, 33, 8, pp. 1894-1900, (2018)
[3]  
Li Bin, Liu Tianqi, Li Xingyuan, Impact of distr-ibuted generation on power system voltage stability, Power System Technology, 33, 3, pp. 84-88, (2009)
[4]  
Dolezal J, Sautarius P, Tlusty J, The effect of dispersed generation on power quality in distribution system, Quality and Security of Electric Power Delivery Systems, CIGRE/IEEE PES International Symposium, pp. 204-207, (2003)
[5]  
Xie Min, Wang Tongwen, Xu Jingdong, Effect of distributed generation on relay protection of distribution network and comprehensive improvement of protection scheme, Power System Protection and Control, 47, 19, pp. 78-84, (2019)
[6]  
Ronan E R, Sudhoff S D, Glover S F, Et al., Ap-plication of power electronics to the distribution transformer, Proceedings of the 15th Annual IEEE Applied Power Electronics Conference and Exposition, pp. 861-867, (2000)
[7]  
Fu Chao, Wu Chengjie, Sun Yuwei, Et al., Hybrid modular DC solid state transformer I: working principle and analysis of steady state characteristics, Transactions of China Electrotechnical Society, 34, 1, pp. 142-152, (2019)
[8]  
Fu Chao, Gao Zhen, Sun Yuwei, Et al., Hybrid modular direct current solid state transformer II: dynamic characteristic and rapid response control, Transactions of China Electrotechnical Soc-iety, 34, 14, pp. 2981-2988, (2019)
[9]  
Zhang Mingrui, Song Baihui, Wang Jiaying, Et al., Control strategy for solid state transformer based on model predictive control, Power System Protection and Control, 47, 1, pp. 129-137, (2019)
[10]  
Zhang Mingrui, Liu Jinhui, Jin Xin, Research on the SVPWM solid state transformer applied in smart micro-grid, Transactions of China Electrotechnical Society, 27, 1, pp. 90-97, (2012)