Multi-port Current Limiting DC Circuit Breaker Based on Voltage Clamp Principle

被引:0
作者
Li G. [1 ]
Song Y. [1 ]
Wang L. [1 ]
Zhao B. [2 ]
Pan Y. [2 ]
Yan K. [1 ]
机构
[1] School of Electrical Engineering, Northeast Electric Power University, Jilin
[2] Tonghua Power Supply Company of State Grid Jilin Electric Power Co., Ltd., Tonghua
[3] Jilin Power Supply Company of State Grid Jilin Electric Power Co., Ltd., Jilin
来源
| 1600年 / Automation of Electric Power Systems Press卷 / 45期
基金
中国国家自然科学基金;
关键词
DC circuit breaker; DC power grid; Fault current limiting; Multi-port; Thyristor; Voltage clamp;
D O I
10.7500/AEPS20201209001
中图分类号
学科分类号
摘要
With the wide application of DC power grid technology, as a key protection device, the DC circuit breaker has become the research focus in the related fields. This paper presents a multi-port current limiting DC circuit breaker based on the voltage clamping principle, which has the advantages of low on-state loss, good economy and fast reclosing speed. Firstly, the topology and operation strategy of the new circuit breaker are proposed, in which the fault is removed by the voltage clamping principle and then the branch thyristors are turned off by LC oscillation. Secondly, the bus and line faults are analyzed and deduced, respectively, and then the parameters are designed according to the shutdown process. Finally, the effectiveness and applicability of the proposed circuit breaker are verified by three-terminal DC network model in PSCAD/EMTDC, and two kinds of fault simulation are analyzed. Through the comparative analysis of fault current, system voltage and branch voltage, it is verified that the proposed circuit breaker can replace several conventional circuit breakers, which can reduce the demand for main circuit breakers. © 2021 Automation of Electric Power Systems Press.
引用
收藏
页码:170 / 178
页数:8
相关论文
共 24 条
[1]  
SHAO Bingbing, ZHAO Shuqiang, GAO Benfeng, Et al., Instability mechanism and criterion of VSC-HVDC connected with weak AC power grid, Transactions of China Electrotechnical Society, 34, 18, pp. 3884-3896, (2019)
[2]  
LI Bin, HE Jiawei, LI Ye, Et al., A review of the protection for the multi-terminal VSC-HVDC grid, Protection and Control of Modern Power Systems, 4, 3, pp. 239-249, (2019)
[3]  
JIN Enshu, WANG Yuechao, XIA Guowu, Et al., An economical MMC topology with DC fault isolation capability, Journal of Northeast Electric Power University, 39, 4, pp. 11-18, (2019)
[4]  
LI Yalou, MU Qing, AN Ning, Et al., Development and challenges of DC power grid model and simulation, Automation of Electric Power Systems, 38, 4, pp. 127-135, (2014)
[5]  
GE Guowei, CHENG Xian, WANG Huaqing, Et al., Criterion of vacuum arc current transfer in low voltage hybrid DC circuit breaker, Transactions of China Electrotechnical Society, 34, 19, pp. 4038-4047, (2019)
[6]  
WEI Xiaoguang, LUO Xiang, ZHOU Wandi, Et al., Design scheme of new high voltage DC circuit breaker for flexible DC transmission network, Automation of Electric Power Systems, 37, 15, pp. 95-102, (2013)
[7]  
ZHENG Xiaoming, WANG Gang, LI Haifeng, Et al., Topology and performance analysis of new combined DC circuit breaker, Automation of Electric Power Systems, 42, 24, pp. 105-117, (2018)
[8]  
TU Chunming, GE Qin, XIAO Fan, Et al., Fault ride through strategy of multi-port solid state transformer based on photovoltaic power supply, Transactions of China Electrotechnical Society, 35, 16, pp. 3498-3508, (2020)
[9]  
TANG Song, JIA Guanlong, ZHANG Chenghao, Et al., Topology of DC circuit breaker with pre-current-limiting capability for DC grid, Automation of Electric Power Systems, 44, 11, pp. 152-162, (2020)
[10]  
LIU Wenjun, LIU Fei, ZHUANG Yizhan, Et al., A multiport circuit breaker-based multiterminal DC system fault protection, IEEE Journal of Emerging and Selected Topics in Power Electronics, 7, 1, pp. 118-128, (2019)