Simplified Small-signal Modeling Method of Grid-connected Inverters and Its Applications

被引:0
作者
Zeng Z. [1 ]
Xiao H. [1 ]
Gao B. [2 ]
Ding J. [2 ]
Wang Z. [1 ]
Hua W. [1 ]
Cheng M. [1 ]
机构
[1] School of Electrical Engineering, Southeast University, Nanjing
[2] State Grid Anhui Electric Power Co., Ltd. Electric Power Research Institute, Hefei
来源
Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering | 2020年 / 40卷 / 21期
基金
中国国家自然科学基金;
关键词
Dq impedance; Grid-connected inverter; Harmonic resonance; Simplified modeling; Stability;
D O I
10.13334/j.0258-8013.pcsee.191617
中图分类号
学科分类号
摘要
With the increasing proportion of distributed generations in distribution networks, harmonic resonance problems caused by interactions between grid-tied inverters and weak grid are becoming increasingly prominent. Small-signal modeling of inverters is the foundation of harmonic stability analysis of the inverter-weak grid coupling system. Based on the small signal model of typical grid-connected inverters in dq coordinate, a simplified impedance modeling method has been proposed in this paper. In the modeling process, matrix operations were reduced and the coupling terms between d and q channels were categorized into negligible and non-negligible parts, so that the connections among inverter impedance terms and the physical segments of inverters can be highlighted to strengthen physical interpretations of dq impedance. In addition, the concepts of active power admittance and reactive power admittance were introduced to demonstrate the influence mechanism of stable operating point's variations on system stability through phase locked loop (PLL). Finally, the theoretical analysis in frequency domain and simulation results in time domain were provided to prove that the proposed simplified impedance model can be used to analyze the resonance mechanism and predict the stability of the inverter-weak grid coupling system. © 2020 Chin. Soc. for Elec. Eng.
引用
收藏
页码:7002 / 7011
页数:9
相关论文
共 27 条
[1]  
Roinila T, Messo T., Online grid-impedance measurement using ternary-sequence injection[J], IEEE Transactions on Industry Applications, 54, 5, pp. 5097-5103, (2018)
[2]  
Zhou Lin, Zhang Mi, Ju Xiuli, Et al., Stability analysis of large-scale photovoltaic plants due to grid impedances, Proceedings of the CSEE, 33, 34, pp. 34-41, (2013)
[3]  
Enslin J H R, Heskes P J M., Harmonic interaction between a large number of distributed power inverters and the distribution network[J], IEEE Transactions on Power Electronics, 19, 6, pp. 1586-1593, (2004)
[4]  
Xie Xiaorong, Liu Huakun, He Jingbo, Et al., Mechanism and characteristics of subsynchronous oscillation caused by the interaction between full-converter wind turbines and AC systems, Proceedings of the CSEE, 36, 9, pp. 2366-2372, (2016)
[5]  
Lu Minghui, Wang Xiongfei, Loh P C, Et al., Resonance interaction of multiparallel grid-connected inverters with LCL filter[J], IEEE Transactions on Power Electronics, 32, 2, pp. 894-899, (2017)
[6]  
Jian Sun, Wang Guoning, Du Xiong, Et al., A theory for harmonics created by resonance in converter-grid systems[J], IEEE Transactions on Power Electronics, 34, 4, pp. 3025-3029, (2019)
[7]  
Wang Xiongfei, Blaabjerg F., Harmonic stability in power electronic-based power systems:concept,modeling,and analysis[J], IEEE Transactions on Smart Grid, 10, 3, pp. 2858-2870, (2019)
[8]  
Yanbo Wang, Wang Xiongfei, Blaabjerg F, Et al., Harmonic instability assessment using state-space modeling and participation analysis in inverter-fed power systems[J], IEEE Transactions on Industrial Electronics, 64, 1, pp. 806-816, (2017)
[9]  
Chen Xin, Wang Yuncheng, Gong Chunying, Et al., Overview of stability research for grid-connected inverters based on impedance analysis method, Proceedings of the CSEE, 38, 7, pp. 2082-2094, (2018)
[10]  