Usage of R513A as an alternative to R134a in a refrigeration system: An experimental investigation based on the Kigali amendment

被引:2
|
作者
Dağıdır K. [1 ]
Bilen K. [2 ]
机构
[1] Tarsus University, Faculty of Engineering, Department of Mechanical Engineering, Mersin
[2] Ankara Yıldırım Beyazıt University, Faculty of Engineering and Natural Sciences, Department of Mechanical Engineering, Ankara
来源
International Journal of Thermofluids | 2024年 / 21卷
关键词
Alternative refrigerant; Energetic analysis; Exergetic analysis; Kigali amendment; R134a; R513A; VCRS;
D O I
10.1016/j.ijft.2024.100582
中图分类号
学科分类号
摘要
In this study, the use of the alternative refrigerant R513A instead of R134a in a mechanical vapor compression refrigeration system was experimentally investigated in terms of the first and second laws of thermodynamics on the basis of the Kigali Amendment. The investigations were carried out approximately at a cooling medium temperature (TL) of 0, 4, and 8 °C and a heating medium temperature (TH) of 30, 35, and 40 °C without any modifications to the system. The energetic and exergetic performance parameters obtained in this study were related to the amount of refrigerant in accordance with the criteria restricting the use of fluorinated greenhouse gases after the Kigali Amendment. Accordingly, the required refrigerant mass flow rate per unit energetic (power input, cooling capacity, COP value) and exergetic (total exergy destruction rate and exergy efficiency) performance parameters were determined. As a result, the system was found to operate safely when R513A was used instead of R134a without any modification. In addition, the refrigerant mass flow rate per unit power input was almost the same for both refrigerants. However, R513A was found to have approximately 15 % more refrigerant mass flow per unit cooling capacity than R134a. This resulted in the refrigerant mass flow rate per unit COP being approximately 20 % higher for R513A. On the other hand, the refrigerant mass flow rate per unit exergy efficiency calculated for R513A was found to be about 15 % higher than R134a. © 2024 The Author(s)
引用
收藏
相关论文
共 50 条
  • [41] Preliminary experimental results on the R134a refrigeration system using a two-phase ejector as an expander
    Ersoy, H. Kursad
    Sag, Nagihan Bilir
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2014, 43 : 97 - 110
  • [42] Energy analysis of vapor compression refrigeration system using mixture of R134a and LPG as refrigerant
    Gill, Jatinder
    Singh, Jagdev
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2017, 84 : 287 - 299
  • [43] Exergy analysis of vapor compression refrigeration system using R450A as a replacement of R134a
    Jatinder Gill
    Jagdev Singh
    Olayinka S. Ohunakin
    Damola S. Adelekan
    Journal of Thermal Analysis and Calorimetry, 2019, 136 : 857 - 872
  • [44] Exergy analysis of vapor compression refrigeration system using R450A as a replacement of R134a
    Gill, Jatinder
    Singh, Jagdev
    Ohunakin, Olayinka S.
    Adelekan, Damola S.
    JOURNAL OF THERMAL ANALYSIS AND CALORIMETRY, 2019, 136 (02) : 857 - 872
  • [45] Experimental investigation of R600a/TiO2/mineral oil as a drop-in replacement for R134a/POE oil in a household refrigeration system
    Babarinde, T. O.
    Akinlabi, S. A.
    Madyira, D. M.
    INTERNATIONAL JOURNAL OF AMBIENT ENERGY, 2019, 43 (01) : 539 - 545
  • [46] Experimental comparison between R152a and R134a working in a refrigeration facility equipped with a hermetic compressor
    Cabello, R.
    Sanchez, D.
    Llopis, R.
    Arauzo, I.
    Torrella, E.
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2015, 60 : 92 - 105
  • [47] Experimental Investigation of Performance of R134a/R152a Refrigerant Mixture in Heat Pump
    Boran, Kurtulus
    Menlik, Tayfun
    Alpsoy, Halil
    JOURNAL OF POLYTECHNIC-POLITEKNIK DERGISI, 2015, 18 (04): : 251 - 256
  • [48] Experimental and Numerical Analyses of R134a Flow Boiling Heat Transfer Characteristics in an Evaporator Tube of Refrigeration System
    Yasser, Zahraa Kareem
    Hamad, Ahmed J.
    INTERNATIONAL JOURNAL OF AIR-CONDITIONING AND REFRIGERATION, 2019, 27 (03)
  • [49] Experimental Investigation of an Automotive Air Conditioning System Using R444A and R152a Refrigerants as Alternatives of R134a
    Direk, Mehmet
    Mert, Mehmet Selcuk
    Soylu, Eren
    Yuksel, Fikret
    STROJNISKI VESTNIK-JOURNAL OF MECHANICAL ENGINEERING, 2019, 65 (04): : 212 - 218
  • [50] Modelling of Refrigerant Distribution in an Oil-Free Refrigeration System using R134a
    Chen, Xinwen
    Li, Zhaohua
    Zhao, Yi
    Jiang, Hanying
    Liang, Kun
    Chen, Jingxin
    ENERGIES, 2019, 12 (24)