Experimental Research on the Air Side Flow and Heat Transfer Characteristics of Natural Draft Dry Cooling Tower Cooling Deltas

被引:0
|
作者
Chen T. [1 ]
Chen Q. [2 ]
Wang L. [1 ]
Qin C. [1 ]
Li W. [3 ]
Han H. [1 ]
Zhao Y. [3 ]
机构
[1] Guodian Zheneng Ningdong Power Generation Co., Ltd., Yinchuan
[2] Jinan Lanchen Energy Technology Co., Ltd., Jinan
[3] School of Energy and Power Engineering, Shandong University, Jinan
基金
中国国家自然科学基金;
关键词
Air flow distribution; Antifreeze; Cooling delta; Crosswind; Dry cooling tower;
D O I
10.13334/j.0258-8013.pcsee.200580
中图分类号
学科分类号
摘要
As the core heat transfer unit of natural draft dry cooling tower (NDDCT), the air side flow and heat transfer characteristics of cooling deltas are very crucial to the overall performance of NDDCT and its system. Based on one real running NDDCT for an air cooling turbo-generator unit about 1000 MW, the field experimental study was carried out around two typical cooling deltas with an intersection angle about 90° between their two angular bisectors. For the two chosen cooling deltas individually located in the windward cooling sector and the lateral cooling sector relative to the local prevailing wind direction, the local face wind velocities, wind temperatures and tube bundle wall temperatures were measured along the windward side of each cooling column, so as to analyze their distribution characteristics and then reveal the generality of cooling delta air side flow and heat transfer characteristics. Gathered data in a long period show that the uneven distribution of air side flow usually exists for most cooling deltas either at the windward side or tower lateral side, which causes the cooling performance difference between the two cooling columns in one cooling delta. Usually, the tube bundle wall temperature is higher for cooling column with lower face wind velocity, where the cooling efficiency is relatively poor. The tube bundle wall temperature is lower for cooling column with higher face wind velocity, where the anti-freezing is essentially required especially in winter. So the aerodynamic field around cooling deltas should be reconstructed to improve its both cooling performance and anti-freezing performance. © 2020 Chin. Soc. for Elec. Eng.
引用
收藏
页码:188 / 194
页数:6
相关论文
共 23 条
  • [1] Calautit J K, Chaudhry H N, Hughes B R, Et al., Comparison between evaporative cooling and a heat pipe assisted thermal loop for a commercial wind tower in hot and dry climatic conditions, Applied Energy, 101, pp. 740-755, (2013)
  • [2] Pan Li, Liu Zhiqiang, Zhang Bo, Comprehensive analysis and related measures on current situation of water saving of thermal power generation in China, Electric Power, 50, 11, pp. 158-163, (2017)
  • [3] Tian Songfeng, Wang Xiandong, Liu Jing, Et al., Numerical simulation in SCAL indirect air-cooling tower in thermal power unit in summer condition, Turbine Technology, 58, 3, pp. 195-197, (2016)
  • [4] Ge Wenjing, Zhao Yuanbin, Song Shiwei, Et al., Thermal characteristics of dry cooling tower reconstructed from obsolete natural draft wet cooling tower and the relevant thermal system coupling optimization, Applied Thermal Engineering, 174, (2020)
  • [5] Zhao Yuanbin, Sun Fengzhong, Li Yan, Et al., Numerical study on the cooling performance of natural draft dry cooling tower with vertical delta radiators under constant heat load, Applied Energy, 149, pp. 225-237, (2015)
  • [6] Zhao Yuanbin, Long Guoqing, Sun Fengzhong, Et al., Effect mechanism of air deflectors on the cooling performance of dry cooling tower with vertical delta radiators under crosswind, Energy Conversion and Management, 93, pp. 321-331, (2015)
  • [7] Zhao Yuanbin, Long Guoqing, Sun Fengzhong, Et al., Numerical study on the cooling performance of dry cooling tower with vertical two-pass column radiators under crosswind, Applied Thermal Engineering, 75, pp. 1106-1117, (2015)
  • [8] Xia Lin, Lu Yang, Liu Zhengwei, Et al., Research on the performance improvement of a natural draft dry cooling tower under crosswind conditions, Turbine Technology, 61, 3, pp. 197-201, (2019)
  • [9] Chen Xuehong, Zhao Yuanbin, Sun Fengzhong, Study on Sensitivity of flow and heat transfer performance of finned tubes bundles to air intake, Power System Engineering, 33, 4, pp. 13-16, (2017)
  • [10] Goudarzi M A., Proposing a new technique to enhance thermal performance and reduce structural design wind loads for natural drought cooling towers, Energy, 62, pp. 164-172, (2013)