A Frequency Estimation Algorithm of Power System Considering Out-of-band Interference

被引:0
|
作者
Bai S. [1 ]
Pan C. [1 ]
Xiong S. [1 ]
Fu L. [1 ]
机构
[1] College of Electrical Engineering, Southwest Jiaotong University, Chengdu, 610031, Sichuan
来源
基金
中国国家自然科学基金;
关键词
DFT; Frequency estimation; Out-of-band interference; Power systems; Taylor model;
D O I
10.13335/j.1000-3673.pst.2018.2766
中图分类号
学科分类号
摘要
Out-of-band interference and fundamental frequency deviation decreases accuracy of frequency estimation sharply, so that a frequency estimation algorithm of power systems considering out-of-band interference was proposed to solve this problem in this paper by modeling frequency deviation of fundamental component and out-of-band interference. Firstly, leakage phenomenon is analyzed considering out-of-band interference and fundamental frequency deviation, and a rough out-of-band phasor is obtained by reassigning phasor estimation of discrete Fourier transform (DFT). Then, the rough phasor was utilized to calculate rough out-of-band frequency, treated as the reference frequency of the expanding Taylor model. Finally, according to the higher-order derivatives of Taylor model, accurate frequency estimation could be obtained. Simulations show that the proposed algorithm can accurately yield both fundamental frequency and out-of-band frequency under frequency deviation and noise disturbance. The power-system-voltage test illustrates that the proposed algorithm can provide frequency estimations with smaller fluctuation than that of the algorithms in comparison. © 2019, Power System Technology Press. All right reserved.
引用
收藏
页码:761 / 768
页数:7
相关论文
共 21 条
  • [1] Shao H., Liu B., Issues in application of 20 Hz voltage injection 100% stator-ground-fault protection, North China Electric Power, 1, 11, pp. 1-5, (2016)
  • [2] Yao Q., Zhao B., Guo B., Et al., Self adaptive stator grounding protection based on injecting 20 Hz electric source signal, Automation of Electric Power Systems, 32, 18, pp. 71-73, (2008)
  • [3] Xie X., Han Y., An overview on power system frequency measurement, Automation of Electric Power Systems, 23, 3, pp. 54-58, (1999)
  • [4] Yao X., Maun J.C., Analysis on error in power system frequency measurement, Power System Technology, 26, 1, pp. 39-42, (2002)
  • [5] IEEE Standard C37.118.1-2011 IEEE standard for synchrophasor measurements for power systems
  • [6] Wang M., Sun Y., A practical, precise method for frequency tracking and phasor estimation, IEEE Transactions on Power Delivery, 19, 4, pp. 1547-1552, (2004)
  • [7] Macii D., Petri D., Zorat A., Accuracy analysis and enhancement of DFT-based synchrophasor estimators in off-nominal conditions, IEEE Transactions on Instrumentation and Measurement, 61, 10, pp. 2653-2664, (2012)
  • [8] Sun Z., Huang J., Yang J., Et al., A high accuracy analysis method for harmonics and inter-harmonics in power systems based on Dolph-Chebyshev windows, Automation of Electric Power Systems, 39, 7, pp. 117-123, (2015)
  • [9] Zeng B., Teng Z., Improved FFT approach for the dynamic state estimation of harmonic parameters based on the Nuttall window, Proceedings of the CSEE, 30, 1, pp. 65-71, (2010)
  • [10] Belega D., Petri D., Accuracy analysis of the multicycle synchrophasor estimator provided by the interpolated DFT algorithm, IEEE Transactions on Instrumentation and Measurement, 62, 5, pp. 942-953, (2013)