Practical Engineering Calculation of Short-circuit Current for Renewable Energy Based on Local Iteration of Fault Area

被引:0
|
作者
Jia K. [1 ]
Hou L. [1 ]
Bi T. [1 ]
Li Y. [2 ]
Qin H. [3 ]
Ding X. [4 ]
机构
[1] State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University, Beijing
[2] State Key Laboratory of Advanced Electromagnetic Engineering and Technology, Huazhong University of Science and Technology, Wuhan
[3] Beijing Sifang Automation Co., Ltd., Beijing
[4] Power Dispatch and Control Center of China Southern Power Grid, Guangzhou
基金
中国国家自然科学基金;
关键词
Fault characteristic analysis; Local iteration; Node voltage; Renewable energy; Short-circuit current calculation;
D O I
10.7500/AEPS20201114003
中图分类号
学科分类号
摘要
With the rapid development of renewable energy, it is transforming from auxiliary power supply to main power supply. There are two problems in the calculation of short-circuit current in the existing renewable energy projects. Firstly, the fault characteristics of renewable energy are characterized by 1.2 to 2 times of rated current, which leads to poor calculation accuracy and is difficult to meet the protection requirements. Secondly, the existing short-circuit current setting calculation software does not support iteration, so it is unable to update the fault current of renewable energy according to the change of node voltage, and reflects the characteristics of voltage controlled current source. To solve this problem, based on the refined analytical model of fault characteristics of renewable energy, combined with the field fault recording data, the voltage-current mapping relationship is constructed to meet the requirements of practical engineering calculation. Then, the fault area is divided according to the degree of node voltage drop and the connection relationship between nodes after the power grid fault, and the local iteration calculation is carried out according to the practical calculation formula of renewable energy in the fault area to solve the node voltage and short-circuit current of the network, so as to avoid the convergence problem caused by the global iteration and shorten the calculation time. Finally, the calculation effect of the proposed method is verified by engineering calculation software. © 2021 Automation of Electric Power Systems Press.
引用
收藏
页码:151 / 158
页数:7
相关论文
共 25 条
  • [1] WANG Chenqing, SONG Guobing, LIU Kai, Et al., Adaptability analysis of mutation protection to wind power integration system, Proceedings of the CSEE, 34, 31, pp. 5485-5492, (2014)
  • [2] JIA Ke, YANG Zhe, WEI Chao, Et al., New energy transmission line pilot protection based on Spearman's rank correlation coefficient, Automation of Electric Power Systems, 44, 15, pp. 103-111, (2020)
  • [3] KROPOSKI B, PINK C, De BLASIO R, Et al., Benefits of power electronic interfaces for distributed energy systems, IEEE Transactions on Energy Conversion, 25, 3, pp. 901-908, (2010)
  • [4] ZHOU Xiaoxin, LU Zongxiang, LIU Yingmei, Et al., Development mode and key technologies of China's future power grid, Proceedings of the CSEE, 34, 29, pp. 4999-5008, (2014)
  • [5] JIA J, YANG G, NIELSEN A H, Et al., Impact of VSC control strategies and incorporation of synchronous condensers on distance protection under unbalanced faults, IEEE Transactions on Industrial Electronics, 66, 2, pp. 1108-1118, (2019)
  • [6] SONG Guobing, TAO Ran, LI Bin, Et al., Overview of power system fault analysis and protection including large-scale power electronic equipment, Automation of Electric Power Systems, 41, 12, pp. 2-12, (2017)
  • [7] FAN Xiaohong, SUN Shiyun, SUN Dejuan, Et al., Analysis of three-phase short circuit current characteristics of doubly fed fan, Power System Protection and Control, 47, 18, pp. 38-48, (2019)
  • [8] KONG Xiangping, ZHANG Zhe, YIN Xianggen, Et al., Fault current characteristics of doubly fed wind turbine considering crowbar protection, Transactions of China Electrotechnical Society, 30, 8, pp. 1-10, (2015)
  • [9] YANG Guosheng, WANG Zengping, OUYANG Jinxin, Et al., Short circuit current calculation method of doubly fed wind turbine considering the whole process of LVRT, Power System Technology, 42, 7, pp. 2185-2193, (2018)
  • [10] KONG X, ZHANG Z, YIN X, Et al., Study of fault current characteristics of the DFIG considering dynamic response of the RSC, IEEE Transactions on Energy Conversion, 29, 2, pp. 278-287, (2014)