Power Distribution System Synchrophasor Measurements with Non-Gaussian Noises: Real-World Data Testing and Analysis

被引:16
作者
Huang C. [1 ]
Thimmisetty C. [2 ]
Chen X. [1 ]
Stewart E. [3 ]
Top P. [1 ]
Korkali M. [1 ]
Donde V. [1 ]
Tong C. [1 ]
Min L. [4 ]
机构
[1] Lawrence Livermore National Laboratory, Livermore, 94550, CA
[2] Palo Alto Networks, Santa Clara, 95054, CA
[3] National Rural Electric Cooperative Association, Arlington, 22203, VA
[4] Precourt Institute for Energy, Stanford University, Stanford, 94305, CA
来源
IEEE Open Access Journal of Power and Energy | 2021年 / 8卷
关键词
Gaussian mixture model (GMM); measurement error; micro-PMU (μPMU); phasor measurement unit (PMU); Power distribution system; state estimation; synchrophasor;
D O I
10.1109/OAJPE.2021.3081503
中图分类号
学科分类号
摘要
This short paper investigates distribution-level synchrophasor measurement errors with online and offline tests, and mathematically and systematically identifies the actual distribution of the measurement errors through graphical and numerical analysis. It is observed that the measurement errors in both online and offline case studies follow a non-Gaussian distribution, instead of the traditionally assumed Gaussian distribution. It suggests the use of non-Gaussian models, such as Gaussian mixture models, for representing the measurement errors more accurately and realistically. The presented tests and analysis are helpful for the understanding of distribution-level measurement characteristics, and for the modeling and simulation of distribution system applications, such as state estimation. © 2020 IEEE.
引用
收藏
页码:223 / 228
页数:5
相关论文
共 21 条
[1]  
Zhang X.-P., Yan Z., Energy quality: A definition, IEEE Open Access J. Power Energy, 7, pp. 430-440, (2020)
[2]  
Liang Z., Et al., Safe reinforcement learning-based resilient proactive scheduling for a commercial building considering correlated demand response, IEEE Open Access J. Power Energy, 8, pp. 85-96, (2021)
[3]  
Duan N., Huang C., Sun C.-C., Min L., Smart meters enabling voltage monitoring and control functionalities: The last-mile voltage stability issue, IEEE Trans. Ind. Informat., (2021)
[4]  
Huang C., Mei J., Bu Q., Su L., FPGA-based adaptive phase-shift compensation method for electronic instrument transformers, Electr. Power Compon. Syst., 45, 7, pp. 774-784, (2017)
[5]  
Sivaranjani S., Agarwal E., Gupta V., Antsaklis P., Xie L., Distributed mixed voltage angle and frequency droop control of microgrid interconnections with loss of distribution-PMU measurements, IEEE Open Access J. Power Energy, 8, pp. 45-56, (2021)
[6]  
Huang C., Et al., Data quality issues for synchrophasor applications. Part I: A review, J. Mod. Power Syst. Clean Energy, 4, 3, pp. 342-352, (2016)
[7]  
Huang C., Et al., Data quality issues for synchrophasor applications. Part II: Problem formulation and potential solutions, J. Mod. Power Syst. Clean Energy, 4, 3, pp. 353-361, (2016)
[8]  
Synchrophasor Monitoring for Distribution Systems: Technical Foundations and Applications, (2017)
[9]  
Duan N., Baone C., Menon A., Dokucu M., Synchrophasor based dynamic model validation leveraging multiple events, Proc. IEEE Power Energy Soc. Innov. Smart Grid Technol. Conf. (ISGT), pp. 1-5, (2018)
[10]  
Wang S., Zhao J., Huang Z., Diao R., Assessing Gaussian assumption of PMU measurement error using field data, IEEE Trans. Power Del., 33, 6, pp. 3233-3236, (2018)