Composite Insulator Energy Transmission Structure for Power Supply of Intelligent Monitoring Instruments

被引:0
|
作者
Huang M. [1 ]
Tang N. [1 ]
Sheng C. [1 ]
Lu Q. [1 ]
Zeng J. [1 ]
机构
[1] Guangdong Diankeyuan Energy Technology Co., Ltd., Guangzhou
来源
关键词
Composite insulator; Intelligent monitoring instruments; PCB resonator; Relay resonator; Wireless power transfer;
D O I
10.13336/j.1003-6520.hve.20200131028
中图分类号
TM72 [输配电技术];
学科分类号
摘要
In order to achieve the stable and uninterrupted power supply of intelligent monitoring instruments for high voltage transmission lines, an energy transmission structure of composite insulators with embedded coils was established based on the wireless power supply system for intelligent monitoring instruments. According to the characteristics of fabrication process of composite insulator and printed circuit board (PCB), a PCB coil board which can be embedded in the insulator was designed, and its embedding characteristics and high voltage insulation performance were verified. On this basis, through mathematical derivation and experimental analysis, the PCB coil board was optimized based on hollow factor and gradual line width. Finally, the design of 110 kV composite insulator energy transmission structure was completed, and experiments were performed to verify its ability. The results show that this new type of composite insulator meets the requirements of high voltage insulation, and can realize the wireless power transmission with distance of 1.13 m. The proposed structure is convenient for production and installation, which can provide a feasible scheme for the design of power supply system of intelligent monitoring instruments. © 2020, High Voltage Engineering Editorial Department of CEPRI. All right reserved.
引用
收藏
页码:618 / 625
页数:7
相关论文
共 24 条
  • [1] Jiang X., Liu Y., Fu X., Et al., Construction ideas and development trends of transmission and distribution equipment of the ubiquitous power internet of things, High Voltage Engineering, 45, 5, pp. 1345-1351, (2019)
  • [2] Liu Z., Global Energy Internet, (2015)
  • [3] Huang X., On-line Monitoring and Fault Diagnosis of Power Transmission Lines, (2008)
  • [4] Fu Y., Rong S., Liu E., Et al., Calibration method and regulation algorithm of binocular distance measurement in the large scene of image monitoring for overhead transmission lines, High Voltage Engineering, 45, 2, pp. 377-385, (2019)
  • [5] Sheng G., Liu Y., Principle and Key Technologies of Intelligent Transmission Line, (2017)
  • [6] Zhu Y., Huang X., Zhang G., Et al., Application research of the power supply for transmission line on-line monitoring devices, High Voltage Apparatus, 54, 7, pp. 231-236, (2018)
  • [7] Sustained rainy weather in the south of China foggy haze in the Fenwei Plain in the middle and south of North China
  • [8] Why is it raining for half a month in March in many parts of South China?
  • [9] Jiang X., Zhang Z., Hu Q., Et al., Thinkings on the restrike of ice and snow disaster to the power grid, High Voltage Engineering, 44, 2, pp. 463-469, (2018)
  • [10] Xiong L., Song D., He Y., Et al., Power supply of online monitoring equipment for transmission line, Electric Power Automation Equipment, 32, 7, pp. 129-133, (2012)