Voltage sag source location estimation based on optimized configuration of monitoring points

被引:12
作者
Lv G. [1 ]
Chu C. [1 ]
Zang Y. [1 ]
Chen G. [1 ]
机构
[1] Electrical Engineering Department, Nanjing Institute of Technology, Nanjing
来源
CPSS Transactions on Power Electronics and Applications | 2021年 / 6卷 / 03期
基金
中国国家自然科学基金;
关键词
Cuckoo search; fault location; fault resistance; optimal configuration of monitoring points; sag source location model; voltage sag;
D O I
10.24295/CPSSTPEA.2021.00023
中图分类号
学科分类号
摘要
In order to reduce the influence of monitoring blind area caused by the uncertainty of fault resistance on voltage sag source location in transmission line short-circuit fault, a voltage sag source location estimation method based on optimal configuration of system monitoring points and fault parameter estimation is proposed. Considering the observability of voltage sag in various short-circuit faults, the importance index of measuring points in the system is proposed, so as to construct the optimal configuration model of monitoring points. Based on the optimal configuration scheme of monitoring points, the sag source location model is established, and the adaptive cuckoo algorithm is used to estimate the parameters of fault line, fault resistance and fault distance. Finally, the simulation is verified by IEEE-30 node standard test system. The results show that the proposed method has higher fault location accuracy and more engineering applicability than the traditional method. © 2017 CPSS.
引用
收藏
页码:242 / 250
页数:8
相关论文
共 27 条
[1]  
Bollen M.H.J., Voltage sags in three-phase systems, IEEE Power Engineering Review, 21, 9, pp. 8-15, (2001)
[2]  
Xiao X.-N., Power Quality Analysis and Control, China Electric Power Press, (2004)
[3]  
Yang H.-G., Xiao X.-Y., Liu J.-G., Issues and technology assessment on power quality, Electric Power Automation Equipment, 23, 12, pp. 1-4, (2003)
[4]  
McGranaghan M., Roettger B., Economic evaluation of power quality, IEEE Power Engineering Review, 22, 2, pp. 8-12, (2002)
[5]  
Ling H.-X., Perfecting power quality indices and prospect, Proceedings of the Csee, 34, 29, pp. 5073-5079, (2014)
[6]  
Kordestani M., Safavi A.A., Saif M., Recent survey of large-scale systems: Architectures, controller strategies, and industrial applications, IEEE Systems Journal, pp. 1-14, (2021)
[7]  
Kordestani M., Saif M., Orchard M.E., Razavi-Far R., Khorasani K., Failure prognosis and applications-A survey of recent literature, IEEE Transactions on Reliability, 70, 2, pp. 728-748, (2021)
[8]  
Espinosa-Juarez E., Hernandez A., Olguin G., An approach based on analytical expressions for optimal location of voltage sags monitors, IEEE Transactions on Power Delivery, 4, 4, pp. 2034-2042, (2009)
[9]  
Lv W., Tian L.-J., Optimal allocation of voltage sag monitoring based on exposed area analysis, Electric Power Automation Equipment, 32, 6, pp. 45-50, (2012)
[10]  
Liao Y., Fault location observability analysis and optimal meter placement based on voltage measurements, Electric Power Systems Research, 79, 7, pp. 1062-1068, (2009)