A Method for Measuring the Zero Sequence Distributed Parameters of Quadruple-Circuit Non-Full-Line Parallel Transmission Lines

被引:0
|
作者
Gao, Mingxin [1 ]
Hu, Zhijian [1 ]
Ni, Shiyuan [2 ]
Zhang, Zhiyi [1 ]
Mou, Hongjiang [1 ]
机构
[1] School of Electrical Engineering and Automation, Wuhan University, Wuhan,430072, China
[2] Institute of Economic and Technology, State Grid Fujian Electric Power Co. Ltd, Fuzhou,350012, China
关键词
Electric lines - Timing circuits - Parameter estimation - Electric power transmission - Computer software;
D O I
暂无
中图分类号
学科分类号
摘要
With the development of power systems, the transmission corridors are becoming narrower, and it is very common for quadruple-circuit lines to share a part of the corridor. There is no corresponding line distributed parameter measurement method. This paper proposes an accurate measurement method for the distribution parameters of quadruple-circuit non-full-line parallel lines, establishes a non-uniform transmission line model of quadruple-circuit non-full-line parallel lines, and obtains the transmission matrix of the quadruple-circuit lines completely through Laplace transform. In addition, the mathematical expressions between the line parameters and the voltages, currents of the heads and ends of the lines are obtained. The zero-sequence voltages and currents of the first end and last end of the quadruple-circuit non-full-line parallel lines are simultaneously measured under four independent measurement modes, and are substituted into the proposed calculation formulae to solve 24 zero-sequence distributed parameters. The accuracy of the proposed method is verified by PSCAD simulation software. Compared with the existing measurement methods, the simulation results show that the proposed method has higher measurement accuracy than the existing methods. © 2022, Electrical Technology Press Co. Ltd. All right reserved.
引用
收藏
页码:1351 / 1364
相关论文
共 42 条
  • [1] New method of measuring the zero-sequence distributed parameters of non-full-line parallel four-circuit transmission lines
    Mou, Hongjiang
    Hu, Zhijian
    Gao, Mingxin
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2022, 139
  • [2] Zero Sequence Parameters Measurement of Triple-circuit Non-full-line Parallel Transmission Lines
    Gao M.
    Hu Z.
    Ni S.
    Liu Y.
    Dianwang Jishu/Power System Technology, 2022, 46 (04): : 1539 - 1547
  • [3] An Approach for Measuring the Zero Sequence Parameters of Mix-Voltage Quadruple-Circuit Transmission Lines on One Tower
    Ni S.
    Hu Z.
    Yang A.
    Fu C.
    Hu, Zhijian (zhijian_hu@163.com), 2018, China Machine Press (33): : 2468 - 2478
  • [4] A New Approach to Measure the Distributed Parameters of Quadruple-Circuit Transmission Lines
    Hu Z.
    Ni S.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2018, 33 (03): : 563 - 572
  • [5] Novel Method of Live Line Measuring the Zero Sequence Parameters of Transmission Lines with Mutual Inductance
    Hu, Zhijian
    Xu, Zhongzhu
    Fan, Jiacheng
    Chen, Mi
    2009 IEEE POWER & ENERGY SOCIETY GENERAL MEETING, VOLS 1-8, 2009, : 1339 - +
  • [6] New Method of Measuring the Zero Sequence Parameters of Double-Circuit EHV/UHV Transmission Lines
    Li, Chuanqi
    Hu, Zhijian
    Jiang, Meiling
    Zhang, Ziyong
    2012 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2012,
  • [7] Research on Mixed Measurement of Zero Sequence Parameters of Parallel Double Circuit Transmission Lines
    Shu, Bin
    Zhang, Pu
    Niu, Shengsuo
    Yu, Xiaoxiao
    Ju, Li
    Proceedings of the 2016 4th International Conference on Mechanical Materials and Manufacturing Engineering (MMME 2016), 2016, 79 : 724 - 726
  • [8] A Interference Measuring Method for Zero Sequence Parameters of Transmission Lines and its Application
    Tang, Jun
    Li, Weiguo
    2012 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2012,
  • [9] Online measuring of zero-sequence parameters for coupled double-circuit transmission line
    Liang, Z. (Zhiruil@sohu.com), 1600, Electric Power Automation Equipment Press (33):
  • [10] Design and Full-scale Test for Steel Tubular Tower of UHV and EHV Quadruple-Circuit Transmission Line on the Same Tower
    Li, Qinghua
    Yang, Jingbo
    Han, Junke
    THERMAL, POWER AND ELECTRICAL ENGINEERING, PTS 1 AND 2, 2013, 732-733 : 1045 - 1051