A quick fault location and isolation method in distribution network based on adaptive reclosure

被引:0
|
作者
Zhang W. [1 ]
Song G. [1 ]
Dou M. [2 ]
Chang Z. [1 ]
Zhang Z. [2 ]
Liu J. [2 ]
Guo S. [3 ]
机构
[1] School of Electrical Engineering, Xi'an Jiaotong University, Xi'an
[2] Electric Power Research Institute of State Grid Shaanxi Electric Power Company, Xi'an
[3] Zhuhai XJ Electric Co., Ltd., Zhuhai
关键词
Adaptive reclosure; Fault isolation and location; Fault phase selector; Phase segregated switch; Voltage-time feeder automation;
D O I
10.19783/j.cnki.pspc.181530
中图分类号
学科分类号
摘要
Feeder automation is important to improve the reliability of distribution network power supply. To solve the problem existed in the voltage-time feeder automation that the fault processing time is long, the upstream switches of the fault point need to tolerate fault current twice and the upstream sections need to experience two short time power outage, a quick fault location and isolation method for distribution network based on adaptive reclosure is proposed in this paper. Three key technologies of the strategy are introduced, including phase selector based on transient current characteristics, a method for distinguishing the transient fault and permanent fault based on the power frequency voltage characteristics, and a phase segregated switch of the distribution network based on the permanent magnet operating structure. The proposed strategy can avoid the second impact on upstream switches and power-off of the upstream section when the fault is permanent, as well as the fault processing time can be effectively shortened. © 2019, Power System Protection and Control Press. All right reserved.
引用
收藏
页码:60 / 67
页数:7
相关论文
共 21 条
  • [1] Liu J., Zhang Z., Zhang X., Investigation on fault processing for electric power distribution networks, Power System Protection and Control, 45, 20, pp. 1-4, (2017)
  • [2] Bo Z., Lin X., Wang Q., Et al., Developments of power system protection and control, Protection and Control of Modern Power Systems, 1, 1, pp. 1-8, (2016)
  • [3] Deng F., Zeng X., Pan L., Research on multi-terminal traveling wave fault location method in complicated networks based on cloud computing platform, Protection and Control of Modern Power Systems, 2, 2, pp. 199-210, (2017)
  • [4] Gopakumar P., Mallikajuna B., Reddy M.T.B., Et al., Remote monitoring system for real time detection and classification of transmission line faults in a power grid using PMU measurements, Protection and Control of Modern Power Systems, 3, 3, pp. 159-168, (2018)
  • [5] Chen Y., Hai T., Voltage type feeder automation system, Power Sysem Technology, 23, 7, pp. 31-33, (1999)
  • [6] Cheng H., Zhang W., Liu J., Improvement of reclosing and instantaneous protection based feeder automation and its setting approach, Automation of Electric Power Systems, 30, 15, pp. 35-39, (2006)
  • [7] EPRI technical report 1010915: technical and system requirements for advanced distribution automation, (2004)
  • [8] Ge L., Tan Z., Zhao F., Et al., An improved feeder self-healing control scheme and its realization, Power System Protection and Control, 41, 18, pp. 62-65, (2013)
  • [9] Zhang Z., Liu J., Zhang X., Et al., Programming of inter-phase short circuit fault processing for distribution automation systems, Power System Protection and Control, 45, 20, pp. 144-148, (2017)
  • [10] Guo S., Song G., Zhang W., Et al., A self-healing solution of single-phase ground fault for distribution network without communication, Distribution & Utilization, 32, 8, pp. 64-70, (2015)