Nonlinear Vibration Behavior and Identification Method for GIS Disconnector Looseness Mechanical Defect Under Variable Frequency Currents Excitation

被引:0
作者
Li X. [1 ]
Hao J. [1 ]
Li Y. [1 ]
Shao Z. [1 ]
Zhong Y. [1 ,2 ]
Jiang X. [3 ]
机构
[1] State Key Laboratory of Power Transmission Equipment Technology, Chongqing University, Chongqing
[2] Scientific Research Institute of Electric Power, Guizhou Power Grid Company Ltd., Guiyang
[3] State Grid Chongqing Electric Power Company Chongqing Electric Power Research Institute, Chongqing
来源
Gaodianya Jishu/High Voltage Engineering | 2024年 / 50卷 / 02期
关键词
defect identification; disconnector; mechanical defects; nonlinear behavior; variable frequency excitation;
D O I
10.13336/j.1003-6520.hve.20230111
中图分类号
学科分类号
摘要
Mechanical defects of gas insulated switchgear(GIS) equipment is one of the critical factors leading to its failure. Therefore, we studied the evolution laws of time domain and frequency domain vibration spectra of disconnector base looseness defects under the excitation of variable frequency currents, and quantitatively analyzed six vibration characteristic values, such as waveform factor and gravity frequency. The support vector machine optimized by the Grey Wolf Optimizer algorithm was used to propose a method for identifiying the severity of GIS disconnector base looseness defects based on variable frequency current excitation mode. The results show that there is a strong correlation between the vibration characteristic values of GIS disconnector base looseness defects and the frequencies of excitation currents. Compared with the single power frequency current excitation mode, variable frequency current excitation has the advantage of more effective detection of GIS mechanical defects. Based on the verification of the 126 kV true GIS experimental platform, the average recognition accuracy of the disconnector base looseness defects identification model is over 90%. The results of this paper provide important references for revealing the nonlinear mechanical vibration characteristics of GIS equipment and improving its mechanical defect detection level. © 2024 Science Press. All rights reserved.
引用
收藏
页码:579 / 589
页数:10
相关论文
共 26 条
[1]  
LI Peng, LI Jinzhong, CUI Boyuan, Et al., Achievements in the newest technology of UHV AC power transmission equipment, High Voltage Engineering, 42, 4, pp. 1068-1078, (2016)
[2]  
HAN Xiancai, SUN Xin, CHEN Haibo, Et al., The overview of development of UHV AC transmission technology in China, Proceedings of the CSEE, 40, 14, pp. 4371-4386, (2020)
[3]  
CUI Jingchun, Gas insulated metal enclosed switchgear, (2016)
[4]  
RUNDE M., Failure frequencies for high-voltage circuit breakers, disconnectors, earthing switches, instrument transformers, and gas-insulated switchgear, IEEE Transactions on Power Delivery, 28, 1, pp. 529-530, (2013)
[5]  
LIU Xin, YAN Nianping, YIN Guilai, Et al., Example analysis of fault classification and cause of UHV GIS defects, Jiangxi Electric Power, 39, 3, pp. 60-63, (2015)
[6]  
FENG Junzong, SUN Lixiong, CHEN Weiwei, Et al., Vibration characteristics of GIS isolating switch under different operating conditions, High Voltage Engineering, 47, 12, pp. 4314-4322, (2021)
[7]  
JI Shengchang, ZHANG Fan, SHI Yuhang, Et al., Review on vibration-based mechanical condition monitoring in power transformers, High Voltage Engineering, 46, 1, pp. 257-272, (2020)
[8]  
DING Dengwei, HE Liang, LONG Wei, Et al., Analysis on vibration mechanisms and detection diagnosis technology of GIS in operating condition, High Voltage Apparatus, 55, 11, pp. 93-99, (2019)
[9]  
WAN Shuting, MA Xiaodi, CHEN Lei, Et al., State evaluation and fault diagnosis of high-voltage circuit breaker based on short-time energy entropy ratio of vibration signal and DTW, High Voltage Engineering, 46, 12, pp. 4249-4257, (2020)
[10]  
ZANG Xu, MA Hongzhong, WU Jinli, Et al., Analysis and diagnosis of a GIS bus conductor loosening based on mechanical vibration, Power System Protection and Control, 49, 9, pp. 12-20, (2021)