Detection Method of HVDC CF Based on Characteristics of Valve-side Current

被引:0
|
作者
Chen G. [1 ]
Fu C. [2 ]
Zhang Y. [1 ]
机构
[1] Guangdong Key Laboratory of Clean Energy Technology, School of Electric Power, South China University of Technology, Guangzhou, 510641, Guangdong Province
[2] State Key Laboratory of HVDC, Electric Power Research Institute, China Southern Power Grid, Guangzhou, 510663, Guangdong Province
来源
基金
中国国家自然科学基金;
关键词
CF; DC transmission; Detection method; Valve-side current;
D O I
10.13335/j.1000-3673.pst.2018.1560
中图分类号
学科分类号
摘要
At present, there is no quick response or reliable detection method for commutation failure (CF) in HVDC systems. In order to solve this problem, the valve-side current that can be directly measured in practical project was used as research object. The CF process at HVDC inverter side was analyzed. The characteristics of valve-side current during CF was derived and 2 cases of the characteristics of valve-side current was summarized. A CF criterion based on the characteristics of valve-side current was proposed, and a CF detection method based on characteristics of valve-side current was designed. Taking CIGRE benchmark HVDC model as an example, CF detection module based on characteristics of valve-side current was established in PSCAD/ EMTDC. The simulation results showed correctness of the analysis of the characteristics of valve-side current during CF, and the proposed method can correctly and quickly detect CF occurrence. © 2019, Power System Technology Press. All right reserved.
引用
收藏
页码:3488 / 3496
页数:8
相关论文
共 21 条
  • [11] Yang J., Tang G., Cao J., Et al., Study on equivalent circuit model for HVDC valve thyristor junction temperature calculation, Proceedings of the CSEE, 33, 15, pp. 156-163, (2013)
  • [12] Krady G., Gilsig T., The calculation of turn-off overvoltages in a high voltage DC thyristor valve, IEEE Transactions on Power Apparatus and Systems, 91, 2, pp. 565-574, (1972)
  • [13] Zhang Y., Qiu L., Shi H., Et al., Fast detection method of commutation failure in multi infeed DC system considering the effect of unbalanced fault, Proceedings of the CSEE, 38, 16, pp. 4759-4767, (2018)
  • [14] Wang Y., Hou Y., Liu F., Et al., Optimization method for startup threshold of commutation failure prevention control considering coordinated recovery of multi-infeed HVDC systems, Automation of Electric Power Systems, 42, 22, pp. 85-90, (2018)
  • [15] Zhou L., Liu T., Zhao T., Et al., Diagnosis of commutation failure in HVDC transmission systems based on voltage or current of converter valve, Power System Technology, 38, 12, pp. 3453-3458, (2014)
  • [16] Yao Q., Li H., Analysis and handling methods of two protection action events in HVDC transmission systems, Automation of Electric Power Systems, 40, 23, pp. 163-167, (2016)
  • [17] Mirsaeidi S., Dong X., Tzelepis D., Et al., A predictive control strategy for mitigation of commutation failure in LCC-based HVDC systems, IEEE Transactions on Power Electronics, PP, 99, (2018)
  • [18] Zhuang W., Li D., Yu Z., Et al., Security and stability control system coping with simultaneous multi-UHVDC commutation failure, Power System Technology, 40, 11, pp. 3420-3426, (2016)
  • [19] Son H.I., Kim H.M., An algorithm for effective mitigation of commutation failure in high-voltage direct-current systems, IEEE Transactions on Power Delivery, 31, 4, pp. 1437-1446, (2016)
  • [20] Xu J., Tan H., Sun H., Et al., Research on method to analyse commutation failure in HVDC power transmission system considering the impact of DC current variation and occurrence moment of AC fault, Power System Technology, 39, 5, pp. 1261-1267, (2015)