Experimental study on an injection-assisted air source heat pump with a novel two-stage variable-speed scroll compressor

被引:0
|
作者
Wang, Jijin [1 ]
Qv, Dehu [2 ]
Ni, Long [1 ]
Yao, Yang [1 ]
机构
[1] School of Architecture, Harbin Institute of Technology, Key Laboratory of Cold Region Urban and Rural Human Settlement Environment Science and Technology, Ministry of Industry and Information Technology, Harbin,150090, China
[2] Department of Building Environment and Energy Application Engineering, School of Civil Engineering, Lanzhou University of Technology, China
来源
Applied Thermal Engineering | 2022年 / 176卷
基金
中国国家自然科学基金;
关键词
Air source heat pumps - Heating - Temperature - Energy efficiency - Pumps;
D O I
暂无
中图分类号
学科分类号
摘要
Traditional air source heat pumps (ASHPs) with scroll compressors were limited in terms of variable volume ratio. An injection-assisted ASHP using a novel two-stage variable-speed scroll compressor with a variable volume ratio and direct current (DC) speed regulation motor, named IDCAHP, was proposed herein for improving heating performance in cold and/or severely cold regions over wide-range temperature conditions. Experiments focusing on the IDCAHP heating performance under different temperatures and various characteristics of the compressor frequency were performed. Results indicated that the IDCAHP performed well over wide-range temperature conditions. In particular, the discharge pressure decreased steadily with falling ambient temperature, and the discharge temperature of the IDCAHP increased with the rising pressure ratio by less than 82.6 °C at an ambient temperature of −20.0 °C. Additionally, gas injection and increasing the compressor frequency could improve the heating capacity of the IDCAHP. As the ambient temperature was −20.0 °C, the heating capacity reached 68.1% of the nominal condition, and the heating coefficient of performance (COP) and energy efficiency ratio (EER) of the IDCAHP could reach 2.0 and 1.8, respectively. Moreover, the decreasing intermediate pressure improved the heating performance. By contrast, with a common ASHP without gas injection, quasi-two-stage compression air-source heat pump with an economiser (QCAHP-E), quasi-two-stage compression air-source heat pump with a flash tank (QCAHP-F), and two-stage compression air-source heat pump (TCAHP) system, the COP of the IDCAHP increased to 35.0%, 4.2%, 37.6%, and 16.2%, respectively, whereas the discharge temperature decreased to 47.9 °C, 46.5 °C, 62.7 °C, and 40.7 °C, respectively. © 2020 Elsevier Ltd
引用
收藏
相关论文
共 50 条
  • [41] Experimental investigation on vapor injection defrosting performance of quasi-two-stage compression air source heat pump with flash tank
    Lin, Musen
    Song, Yiping
    Wu, Lintao
    Ni, Long
    APPLIED THERMAL ENGINEERING, 2024, 244
  • [42] Two-stage air-source heat pump for residential heating and cooling applications in northern US climates
    Bertsch, Stefan S.
    Groll, Eckhard A.
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2008, 31 (07): : 1282 - 1292
  • [43] Experimental study of an organic Rankine cycle with a variable-rotational-speed scroll expander at various heat source temperatures
    Hsieh, Jui-Ching
    Chen, Yen-Hsun
    Hsieh, Yi-Chi
    ENERGY, 2023, 270
  • [44] The experimental analysis of the effect of ambient factors on the defrosting of economised vapour injection compressor air source heat pump in marine climates
    Huang, M. J.
    Hewitt, N. J.
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2013, 36 (03): : 820 - 827
  • [45] A proof-of-concept study of a novel ventilation heat recovery vapour injection air source heat pump
    Fan, Yi
    Li, Jing
    Zhao, Xudong
    Myers, Steve
    Cheng, Yuanda
    Yu, Min
    Akhlaghi, Yousef Golizadeh
    Ma, Xiaoli
    Yu, Sen
    ENERGY CONVERSION AND MANAGEMENT, 2022, 256
  • [46] A novel two-stage compression air-source heat pump cycle combining space heating, cooling, and domestic hot water production
    Liu, Jian
    Zhou, Lu
    Cheng, Jianhong
    Lin, Zhang
    Zhang, Xiaosong
    ENERGY AND BUILDINGS, 2023, 285
  • [47] Experimental study of enhancing heating performance of the air-source heat pump by using a novel heat recovery device designed for reusing the energy of the compressor shell
    Huang, Bi
    Jian, Qifei
    Luo, Lizhong
    Zhao, Jing
    ENERGY CONVERSION AND MANAGEMENT, 2017, 138 : 38 - 44
  • [48] A modeling study on developing the condensing-frosting performance maps for a variable speed air source heat pump
    Liu, Shengnan
    Bai, Xiaoxia
    Deng, Shiming
    Zhang, Long
    Wei, Minchen
    JOURNAL OF BUILDING ENGINEERING, 2022, 58
  • [49] The selection of volume ratio of two-stage rotary compressor and its effects on air-to-water heat pump with flash tank cycle
    Ko, Younghwan
    Park, Sangkyoung
    Jin, Simon
    Kim, Byungsoon
    Jeong, Ji Hwan
    APPLIED ENERGY, 2013, 104 : 187 - 196
  • [50] Control strategy and experimental study on a novel defrosting method for air-source heat pump
    Liang, Cai-Hua
    Zhang, Xiao-Song
    Li, Xiu-Wei
    Chen, Zhen-Qian
    APPLIED THERMAL ENGINEERING, 2010, 30 (8-9) : 892 - 899