FAULT LOCATION BASED ON COMPREHENSIVE GREY RELATIONAL DEGREE FOR FLEXIBLE DC DISTRIBUTION NETWORK

被引:0
|
作者
Xu Y. [1 ]
Hu Z. [1 ]
Dong H. [1 ]
Ma T. [2 ]
机构
[1] State Key Laboratory of New Energy and Electric Power Systems, North China Electric Power University, Baoding
[2] State Grid Hebei Electric Power Co.,Ltd., Electric Power Research Institute, Shijiazhuang
来源
关键词
DC distribution network; fault location; grey relational degree; relativity; travelling differential current;
D O I
10.19912/j.0254-0096.tynxb.2021-1416
中图分类号
学科分类号
摘要
In order to solve the problem of high accuracy and rapidity requirements for fault location in flexible DC distribution networks,a fault location method for flexible DC distribution network based on grey relational degree is proposed. The similarity of the first and last line mode traveling wave differential current waveforms is analyzed using grey relational degree,and the fault location is achieved by solving the optimal time shift. Finally,a six-terminal flexible DC distribution network model is built in Matlab/Simulink for simulation and validation,showing that the method can complete the rapid and accurate location of all types of faults on the whole line,and has a certain resistance to transition resistance,suitable for the case of low sampling frequency,and has high reliability. © 2023 Science Press. All rights reserved.
引用
收藏
页码:324 / 331
页数:7
相关论文
共 18 条
  • [1] WANG X G, XIAO L Y., Comprehensive control strategy of LCL- based Z- source photovoltaic grid- connected inverter [J], Acta energiae solaris sinica, 37, 11, pp. 2965-2972, (2016)
  • [2] SUN P F,, HE C G,, SHAO H, Et al., Research status and development of DC distribution network[J], Electric power automation equipment, 36, 6, pp. 64-73, (2016)
  • [3] XIONG X, LI R,, Et al., An overview of key technology and demonstration application of DC distribution and consumption system[J], Proceedings of the CSEE, 38, 23, pp. 6802-6813, (2018)
  • [4] LI P F, LI X L, WANG C S,, Review of stability analysis model and mechanism research of medium-and low- voltage flexible DC distribution system[J], Electric power automation equipment, 41, 5, pp. 3-21, (2021)
  • [5] XU Y, CHENG S, XUE Y J., Longitudinal protection scheme based on the Pearson correlation coefficient of fault transient current [J], Journal of North China Electric Power University(natural sciences edition), 48, 4, pp. 11-19, (2021)
  • [6] XU Y, LIU J Y,, ZHANG S H,, Et al., Fault location method based on genetic algorithm foe DC distribution network[J], Acta energiae solaris sinica, 41, 12, pp. 1-8, (2020)
  • [7] Travelling waves-based fault location scheme for feeders in power distribution network[J], The journal of engineering, 2018, 15, pp. 1326-1329, (2018)
  • [8] LI B, ZHANG J H, LIU H J,, Et al., Fault location of HVDC transmission lines based on waveform similarity analysis[J], Electric power automation equipment, 39, 9, pp. 27-32, (2019)
  • [9] ZHAO W., Research on Lissajous graph fault diagnosis method of high- voltage cable based on grey correlation analysis[D], (2020)
  • [10] TONG X Y, ZHANG S X., Grey relational degree based fault section location and type recognition method for distribution network[J], Automation of electric power systems, 43, 4, pp. 113-118, (2019)