Optimal Configuration of Synchronous Condensers for Suppressing Multi-infeed DC Commutation Failure

被引:0
|
作者
Jian W. [1 ]
Zhou Z. [2 ]
Tang F. [1 ]
Liu D. [1 ]
Wang C. [1 ]
Liang W. [1 ]
机构
[1] School of Electrical Engineering and Automation, Wuhan University, Wuhan
[2] State Grid Zhejiang Electric Power Research Institute, Hangzhou
来源
关键词
Commutation failure; Multi-infeed DC system; Optimal allocation; Reactive power support; Synchronous condenser;
D O I
10.13336/j.1003-6520.hve.20200528002
中图分类号
学科分类号
摘要
After the AC side short-circuit fault occurs in a multi-infeed DC system, the voltage of the AC system will continue to decrease, and will thus cause the commutation failure of multiple or even simultaneous failure of all DCs, which will seriously damage the security and stability of the power grid. The synchronous condenser has overload capability, and its reactive output is negligibly affected by the system voltage. The voltage drop caused by the AC fault can provide strong reactive power support, and can thereby suppress the occurrence of DC commutation failure. To suppress the failure of DC commutation, a synchronous condenser optimization configuration method for suppressing multi-feed DC commutation failure was proposed, which was optimized for both installation location and capacity. Firstly, starting from the duration of DC commutation failure, and taking the interaction between DCs into account, we proposed an effective index for suppressing commutation failure. Then, according to the electrical distance, the area to be selected was determined, and the best compensation location of synchronous condenser was selected by the reactive compensation response index.Thirdly, the configuration optimization model of synchronous condenser was established, and the optimal configuration scheme was solved in two stages to obtain the final configuration scheme. Finally, the actual large-grid simulation results show that the final solution can effectively suppress the multi-feed DC commutation failure caused by AC fault while considering economy. © 2021, High Voltage Engineering Editorial Department of CEPRI. All right reserved.
引用
收藏
页码:169 / 177
页数:8
相关论文
共 25 条
  • [1] YANG Haitao, JI Ping, LIU Jinxiong, Et al., Analysis on the functionand reliability of UHV grid-frame schemes, High Voltage Engineering, 43, 3, pp. 1014-1022, (2017)
  • [2] LIU Zhenya, QIN Xiaohui, ZHAO Liang, Et al., Study on the applicationof UHVDC hierarchical connection mode to multi-infeed HVDCsystem, Proceedings of the CSEE, 33, 10, pp. 1-7, (2013)
  • [3] WANG Jing, LIANG Zhifeng, JIANG Mu, Et al., Case analysis andsimulation of commutation failure in multi-infeed HVDC transmissionsystems, Automation of Electric Power Systems, 39, 4, pp. 141-146, (2015)
  • [4] GUO Chunyi, ZHAO Jian, LIU Wei, Et al., A review ofmethods to mitigate the commutation failure forLCC-HVDC, Proceedings of the CSEE, 38, pp. 1-10, (2018)
  • [5] WANG Yating, ZHANG Yichi, ZHOU Qinyong, Et al., Study on application of new generation large capacity synchronous condenser in powergrid, Power System Technology, 41, 1, pp. 22-28, (2017)
  • [6] SHA Jiangbo, ZHAO Chengyong, WANG Qing, Et al., Impact of synchronous condensers on maximum available power of UHVDC system, High Voltage Engineering, 45, 11, pp. 3627-3634, (2019)
  • [7] XIAO Jun, LI Xingyuan, FENG Ming, Et al., Determination of installationsites for reactive compensation devices in multi-infeed AC/DCpowersystem, Power System Technology, 38, 10, pp. 2638-2643, (2014)
  • [8] JIN Yiding, YU Zhao, LI Mingjie, Et al., Comparison of new generation synchronous condenser and power electronic reactive-power compensation devices in application in UHV DC/AC grid, Power System Technology, 42, 7, pp. 2095-2102, (2018)
  • [9] ZHANG Hongli, LIU Fusuo, LI Wei, Site selection for dynamic reactive power compensation and improvement of recovery fromcommutation failures in multi-infeed HVDC system, Automation of Electric Power Systems, 40, 5, pp. 133-138, (2016)
  • [10] WANG Qiang, LI Tianran, TANG Xiaobo, Et al., Method of site selection for synchronous condenser responding to commutation failures of multi-infeed DC system, Automation of Electric Power Systems, 43, 1, pp. 222-229, (2019)