Modeling and Analysis of Arc Grounding Faults in Isolated Neutral Distribution Network

被引:0
|
作者
Ren, Wei [1 ]
Xue, Yongduan [1 ]
Yang, Fan [2 ]
Xu, Bingyin [3 ]
机构
[1] College of New Energy, China University of Petroleum (East China), Qingdao,266580, China
[2] Electric Power Research Institute of State Grid Hubei Electric Power Co., Ltd., Wuhan,430077, China
[3] Research Center for Smart Grid (Shandong University of Technology), Zibo,255049, China
来源
基金
中国国家自然科学基金;
关键词
Timing circuits - Power quality - Electric grounding;
D O I
暂无
中图分类号
学科分类号
摘要
The single-phase arc grounding faults are common in isolated neutral distribution network, it is necessary to model and analyze its nonlinear characteristics in a proper way. The traditional methods rely on the simulation analysis of the arc black box model which is difficult to quantify the effects of arc non-linearity on fault transient characteristics. In order to solve this problem, this paper follows the idea of simplifying the arc model by retaining main features of the middle and low frequency of the arc, and proposes a Multi-odd frequency voltage source equivalent arc model which is more suitable for fault transient and steady state analysis. Then, combined with the transient equivalent circuit of isolated neutral distribution network, analytical expression of transient current in arc grounding faults under different fault resistances is quantitatively calculated, and the harmonic characteristics of the stable current of the fault are analyzed. The effectiveness of the new method is verified by simulation and experiment data. It provides a theoretical basis for subsequent research on arc grounding faults protection under different neutral grounding modes. © 2021, Power System Technology Press. All right reserved.
引用
收藏
页码:705 / 712
相关论文
共 50 条
  • [21] Distribution system neutral grounding
    Burke, J
    Marshall, A
    2001 IEEE/PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXPOSITION, VOLS 1 AND 2: DEVELOPING NEW PERSPECTIVES, 2001, : 166 - 170
  • [22] Influence analysis of neutral point grounding mode on the single-phase grounding fault characteristics of distribution network with distributed generation
    Feng, Bo
    Jia, Yong
    Chen, Yan
    Zhong, Jiayong
    Shi, Jiawei
    Gu, Feiqiang
    Luo, Jian
    2020 5TH ASIA CONFERENCE ON POWER AND ELECTRICAL ENGINEERING (ACPEE 2020), 2020, : 1834 - 1840
  • [23] Detection of Arc Grounding Fault in Distribution Network Based on the Harmonic Component
    Zhang, Bingwei
    Sun, Yuanyuan
    Shi, Fang
    Zhang, Hengxu
    Liu, Shu
    Zhang, Yong
    PROCEEDINGS OF THE 2018 13TH IEEE CONFERENCE ON INDUSTRIAL ELECTRONICS AND APPLICATIONS (ICIEA 2018), 2018, : 2559 - 2564
  • [24] Transient Characteristics and Influence of Small Current Grounding Faults in Active Distribution Network
    Qin S.
    Xue Y.
    Liu L.
    Guo Y.
    Xu M.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2022, 37 (03): : 655 - 666
  • [25] Analysis of distribution network line relay protection during single-phase high-resistance grounding faults in low resistance neutral grounded system
    Xu, Qingqiang
    Xu, Yang
    Zhou, Dongji
    Xi, Xuefeng
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2010, 34 (09): : 91 - 94
  • [26] Modeling and simulation of arc grounding fault of middle and low voltage distribution network based on ATP-EMTP
    Xu, Xiangzheng
    Hu, Wenguang
    JOURNAL OF COMPUTATIONAL METHODS IN SCIENCES AND ENGINEERING, 2020, 20 (04) : 1279 - 1288
  • [27] Simulation of Arc Grounding Over-voltage Based on MODELS and TACS for Neutral Isolated Systems
    Jin, E. S.
    Yang, M. F.
    Bo, Z. Q.
    Klimek, A.
    2009 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), VOLS 1-7, 2009, : 3511 - +
  • [28] Active Fault Locating Method Based on SOP for Single Phase Grounding Faults in the Resonant Grounding Distribution Network
    Ye Y.
    Ma X.
    Lin X.
    Li Z.
    Xu F.
    Wang C.
    Ni X.
    Ding C.
    Ma, Xiao (1815708181@qq.com), 1600, Chinese Society for Electrical Engineering (40): : 1453 - 1464
  • [29] Establishment of Intermittent Reignition Arc Model and Analysis of Intermittent Arcing Ground Faults in Distribution Network
    Zhang B.
    Zhou S.
    Wu X.
    Hou B.
    Hou H.
    Qiu J.
    Ding X.
    Dianwang Jishu/Power System Technology, 2024, 48 (05): : 2207 - 2217
  • [30] Modeling underground lines as components of distribution network grounding systems
    Rajicic, D
    Ackovski, R
    Eurocon 2005: The International Conference on Computer as a Tool, Vol 1 and 2 , Proceedings, 2005, : 1255 - 1258