Single-phase earth fault protection method based on combined voltage criterion in high voltage shunt capacitor

被引:0
作者
Ma W. [1 ]
Kong S. [1 ]
Liu C. [1 ]
Song C. [1 ]
Liu Y. [1 ]
机构
[1] State Grid Henan Electric Power Research Institute, Zhengzhou
来源
Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control | 2019年 / 47卷 / 22期
关键词
Combined voltage; Comparing; Shunt capacitor; Single-phase earth fault; Voltage phase; Voltage value;
D O I
10.19783/j.cnki.pspc.181608
中图分类号
学科分类号
摘要
In allusion to the insufficiency of capacitor bank single-phase fault protection at present, this paper puts forward a combined voltage criterion protection method by comparing three-phase ground voltage to distinguish the single-phase earth fault. Aiming at constructing combined voltage criterion, voltage value comparison method and voltage phase comparison method are analyzed theoretically and a protection setting calculation method is given. Through analyzing and comparing the advantage and disadvantage of the two methods, voltage value comparison method is recommended to construct the combined voltage criterion. Furthermore, the feasibility of combined voltage criterion is verified by simulation. Since the protection will act only if all the three phase voltages are satisfied, the combined voltage criterion has a better function to prevent protection misoperation caused by PT breaking. © 2019, Power System Protection and Control Press. All right reserved.
引用
收藏
页码:142 / 147
页数:5
相关论文
共 21 条
[1]  
Ma L., Qian L., Impact of harmonics on the internal fault protections of assembling capacitor, Power System Protection and Control, 38, 5, pp. 87-90, (2010)
[2]  
Chen Q., Liu J., Analysis on colony fusing failure of 35 kV parallel capacitors and parameters set on its zero sequence difference current protection, Power System Protection and Control, 38, 11, pp. 67-74, (2010)
[3]  
Sun L., Weng H., Design of online monitoring system for shunt capacitors based on differential voltage, Power System and Clean Energy, 28, 2, pp. 16-20, (2012)
[4]  
Li T., Wang G., Zhou X., Establishment of simulation model of shunt capacitor bank and case analysis, Guangxi Electric Power, 40, 4, pp. 6-9, (2017)
[5]  
Gan J., Wang Z., Lin Y., Research on the implementation scheme of shunt capacitor protection and monitoring, Electric Power Science and Engineering, 33, 5, pp. 11-15, (2017)
[6]  
Ma X., Fan X., Hu F., Et al., Design of a new type of high voltage shunt capacitor on line monitoring system, Memoir of Electric Power Quality and Saving, pp. 161-164, (2017)
[7]  
Zhang J., Yuan J., Sun H., Et al., Research on protection mode of shunt capacitors at 35 kV and above, Power Capacitor & Reactive Power Compensation, 35, 5, pp. 16-20, (2014)
[8]  
Wang Y., Meng R., Wang Y., Et al., Problems on settings of shunt capacitor bank protection in 500 kV substation, Electric Power Automation Equipment, 30, 8, pp. 144-147, (2010)
[9]  
Xian J., Study on the protection configuration and reliability analysis of shunt capacitor, (2015)
[10]  
Bai Y., Study on the setting calculation and fault analysis of high voltage shunt capacitor banks, (2015)